Schneider-Electric
 
A9N18372 picture- Schneider-electric
A9N18372
C120N - circuit breaker - 4P - 80A - C curve
Schneider Electric
Characteristics
Main
Range of product C120
Range Acti 9
Product name C120
Product or component type Miniature circuit-breaker
Device short name C120N
Device application Distribution
Poles description 4P
Number of protected poles 4
[In] rated current 80 A at 30 °C
Network type AC
Trip unit technology Thermal-magnetic
Curve code C
Breaking capacity 6 kA Icu conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
10 kA Icu conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz
20 kA Icu conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz
10 kA Icu conforming to EN/IEC 60947-2 - <= 500 V DC
10000 A Icn conforming to EN/IEC 60898-1 - 230...400 V AC 50/60 Hz
Suitability for isolation Yes conforming to IEC 60947-2
Complementary
Network frequency 50/60 Hz
[Ue] rated operational voltage <= 500 V DC
220...240 V AC 50/60 Hz
380...415 V AC 50/60 Hz
440 V AC 50/60 Hz
230...400 V AC 50/60 Hz
Magnetic tripping limit 5...10 x In
[Ics] rated service breaking capacity 4.5 kA at 75 % of breaking cap. conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
7.5 kA at 75 % of breaking cap. conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz
15 kA at 75 % of breaking cap. conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz
7500 A at 75 % of breaking cap. conforming to EN/IEC 60898-1 - 230...400 V AC 50/60 Hz
10 kA at 100 % of breaking cap. conforming to EN/IEC 60947-2 - <= 500 V DC
Limitation class 3 conforming to EN/IEC 60947-2
[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2
Contact position indicator Yes
Control type Toggle
Local signalling ON/OFF indication
Mounting mode Clip-on
Mounting support 35 mm symmetrical DIN rail
Comb busbar and distribution block compatibility YES
9 mm pitches 12
Height 81 mm
Width 108 mm
Depth 73 mm
Product weight 0.82 kg
Colour White
Mechanical durability 20000 cycles
Electrical durability 5000 cycles conforming to IEC 60947-2
Connections - terminals Tunnel type terminals 1.5...35 mm² flexible
Tunnel type terminals 1...50 mm² rigid
Wire stripping length 15 mm
Tightening torque 3.5 N.m
Earth-leakage protection Separate block
Environment
Standards EN/IEC 60947-2
EN/IEC 60898-1
Product certifications EAC
IP degree of protection IP20 conforming to IEC 60529
Pollution degree 3 conforming to IEC 60947-2
Overvoltage category IV
Tropicalisation 2 conforming to IEC 60068-1
Relative humidity 95 % 55 °C
Operating altitude 2000 m
Ambient air temperature for operation -25...70 °C
Ambient air temperature for storage -40...85 °C
Offer Sustainability
RoHS (date code: YYWW) Compliant  - since  0627  -  Schneider Electric declaration of conformity
print Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Contractual warranty
Warranty period 18 months