Terminal block type
|
Removable
|
Isolation PLC/operative part
|
No
|
Fixing mode
|
By clips (35 mm symmetrical DIN rail)
By screws (solid plate with fixing kit)
|
Current state 0 guaranteed
|
0.4 mA (PLC end)
|
Voltage state 0 guaranteed
|
3.4 V for PLC end
|
Current state 1 guaranteed
|
3.1 mA (PLC end)
|
Voltage state 1 guaranteed
|
16.9 V for PLC end
|
Maximum current per output common
|
8 A
|
Current per channel
|
0.5 A for preactuator end
|
Minimum switching current
|
1 mA
|
Drop-out voltage
|
0.6 V (preactuator end)
|
Maximum switching current
|
500 mA DC-12
500 mA DC-13
|
Maximum tungsten load
|
<10 W DC-6
|
Maximum residual current
|
0.3 mA preactuator end
|
Fault type
|
Overload
Short-circuit
|
Fault indication
|
Yes
|
Switchable inductive energy L/R
|
<= 400(U.I) ms
|
Maximum circuit breaker threshold
|
0.75 A
|
Response time
|
<= 0.02 ms from state 1 to 0
<= 0.1 ms from state 0 to 1
|
Switching frequency
|
< 0.6/LI² Hz
|
Installation category
|
II conforming to IEC 60664-1
|
Tightening torque
|
0.6 N.m with flat Ø 3.5 mm screwdriver
|
Width
|
206 mm
|
Net weight
|
0.405 kg
|
Product certifications
|
UL
GL
CSA
DNV
EAC
|
IP degree of protection
|
IP2X conforming to IEC 60529
|
Protective treatment
|
TC
|
Resistance to incandescent wire
|
750 °C, extinction time <30 s conforming to IEC 60695-2-11
|
Shock resistance
|
15 gn for 11 ms conforming to IEC 60068-2-27
|
Resistance to radiated fields
|
10 V/m (26000000…1000000000 Hz) conforming to IEC 61000-4-3 level 3
|
Resistance to fast transients
|
2 kV level 3 conforming to IEC 61000-4-4
|
Ambient air temperature for operation
|
-5…60 °C conforming to IEC 61131-2
|
Ambient air temperature for storage
|
-40…80 °C conforming to IEC 61131-2
|
Pollution degree
|
2 conforming to IEC 60664-1
|