ABL8BBU24400
battery control module, phaseo ABL7 ABL8, 24 to 28.8V DC, phaseo ABL7 ABL8, 24V, 40A, for regulated SMPS
|
|
|
|
|
|
|
End of Commercialization MAR 31, 2025
|
|
|
Main
Range of product
|
Phaseo
|
Product or component type
|
Battery control module
|
Input voltage
|
24...28.8 V DC
|
Output voltage
|
(Ubattery-0.5) V in battery mode DC
(Uin-0.25) V in nominal mode DC
|
Maximum output current
|
40 A
|
Complementary
Input voltage limits
|
22...30 V
|
Maximum power dissipation in W
|
12 W
|
Activation threshold
|
Adjustable 22...36 V
|
Number of output channels
|
1
|
Current consumption
|
0.6 A on load
0.1 mA no load
<= 40.6 A
|
Output protection type
|
Against overload, protection technology: 1.5 x In
Against short-circuits, protection technology: battery-backed mode, automatic reset
Against short-circuits, protection technology: power-supplied mode
|
Connections - terminals
|
For diagnostic relay: removable screw terminal block, connection capacity: 1 x 0.75 mm²
For input connection: screw type terminals, connection capacity: 2 x 0.5...2 x 10 mm² AWG 20...AWG 8
For output connection: screw type terminals, connection capacity: 2 x 0.5...2 x 10 mm² AWG 20...AWG 8
|
Fixing mode
|
By clips on 35 mm symmetrical DIN rail, operating position: horizontal
By clips on 35 mm symmetrical DIN rail, operating position: vertical
|
Marking
|
CE
|
Name of test
|
Electrostatic discharges conforming to IEC 61000-4-2
Emission conforming to IEC 61000-6-3
Induced electromagnetic field conforming to IEC 61000-4-6 level 3
Radiated electromagnetic field conforming to IEC 61000-4-3 level 3
Rapid transient conforming to IEC 61000-4-4 level 3
Surge conforming to IEC 61000-4-5 level 2
Conducted/radiated emissions conforming to EN 55022 class B, 20 %
|
Local signalling
|
1 C/O relay for alarm status
1 C/O relay for battery status
1 C/O relay for power supply status
LCD screen for module status
|
Net weight
|
0.7 kg
|
Environment
Product certifications
|
RCM
EAC
|
Standards
|
UL 508
CSA C22.2 No 60950-1
|
Ambient air temperature for operation
|
-25…60 °C
|
Ambient air temperature for storage
|
-40…85 °C
|
Environmental characteristic
|
EMC conforming to IEC 61000-6-3
EMC conforming to IEC 61000-6-2
Safety conforming to IEC 60950-1
Safety conforming to EN/IEC 61204-3
|
IP degree of protection
|
IP20 conforming to IEC 60529
|
Dielectric strength
|
500 V between input and ground
500 V between output and ground
|
Overvoltage category
|
Class II conforming to VDE 0106-1
|
Relative humidity
|
0…90 % during operation
0…95 % during storage
|
MTBF reliability
|
707945 H at 24 V DC with UTE C80-810 calculation method
|
Vibration resistance
|
2 gn (f= 11.9…150 Hz) conforming to IEC 61131-2
3.5 mm (f= 3…11.9 Hz) conforming to IEC 61131-2
|
Packing Units
Unit Type of Package 1
|
PCE
|
Number of Units in Package 1
|
1
|
Package 1 Height
|
11.2 cm
|
Package 1 Width
|
18 cm
|
Package 1 Length
|
18.5 cm
|
Package 1 Weight
|
1.349 kg
|
Unit Type of Package 2
|
S04
|
Number of Units in Package 2
|
8
|
Package 2 Height
|
30 cm
|
Package 2 Width
|
40 cm
|
Package 2 Length
|
60 cm
|
Package 2 Weight
|
12.11 kg
|
Offer Sustainability
SCIP Number
|
D3d88924-119f-4532-b002-d5104837eddb
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Pro-active compliance (Product out of EU RoHS legal scope)
|
Mercury free
|
Yes
|
RoHS exemption information
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
California proposition 65
|
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
|
Contractual warranty
|
|