Input voltage limits
|
90...264 V AC
|
Nominal network frequency
|
50…60 Hz
|
Network system compatibility
|
TN
TT
IT
|
Maximum leakage current
|
1 mA 240 V AC
|
Input protection type
|
Integrated fuse (not interchangeable) 4 A
|
Inrush current
|
45 A at 115 V
85 A at 230 V
|
Power factor
|
0.55 at 115 V AC
0.45 at 230 V AC
|
Efficiency
|
89 % at 230 V AC
|
Output voltage adjustment
|
21.6...26.4 V
|
Power dissipation in W
|
20 W
|
Current consumption
|
< 2.3 A 115 V AC
< 1.5 A 230 V AC
|
Turn-on time
|
< 500 ms
|
Holding time
|
> 20 ms 115 V AC
> 40 ms 230 V AC
|
Startup with capacitive loads
|
4000 µF
|
Residual ripple
|
< 150 mV
|
Meantime between failure [MTBF]
|
700000 h at 25 °C, full load conforming to SR 332
|
Output protection type
|
Against overload and short-circuits, protection technology: automatic reset
Against over temperature, protection technology: manual reset
Against overvoltage, protection technology: manual reset
|
Connections - terminals
|
Screw connection: 0.75...2.5 mm², (AWG 18...AWG 14) without wire end ferrule
Screw connection: 0.75...1.5 mm², (AWG 18...AWG 16) with wire end ferrule
|
Line and load regulation
|
< 0.5 % at 0 to 100 % load at 25 °C
< 1 % at full voltage range in line at 25 °C
|
Status LED
|
1 LED (green) output voltage
|
Depth
|
129 mm
|
Height
|
30 mm
|
Width
|
97 mm
|
Net weight
|
0.3 kg
|
Output coupling
|
Parallel
Serial
|
Mounting support
|
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
Double-profile DIN rail
Panel mounting
|
Supply
|
SELV conforming to IEC 60950-1
SELV conforming to IEC 60204-1
SELV conforming to IEC 60364-4-41
|
Dielectric strength
|
3750 V AC with input to output
|
Service life
|
10 year(s)
|
Overvoltage category
|
II
|
Standards
|
IEC 62368-1
IEC 61010-1
EN 61010-2-201
EN 61204-3
IEC 61000-6-1
IEC 61000-6-2
IEC 61000-6-3
IEC 61000-6-4
IEC 61000-3-2
EN 61000-3-3
UL 62368-1
UL 61010-1
UL 61010-2-201
CSA C22.2 No 62368-1
CSA C22.2 No 61010-1
CSA C22.2 No 61010-2-201
EN/IEC 62368-1
|
Product certifications
|
CE
CULus
EAC
RCM
CB Scheme
KC
|
Operating altitude
|
5000 m
|
Shock resistance
|
150 m/s² for 11 ms
|
IP degree of protection
|
IP10
|
Ambient air temperature for operation
|
-30…50 °C without derating mounting position A, B, F, G < 2000 m
50…70 °C with current derating of 2 % per °C mounting position A, B, F, G < 2000 m
|
Electrical shock protection class
|
Class I
|
Pollution degree
|
2
|
Vibration resistance
|
3 mm (f= 2…9 Hz) conforming to IEC 60068-2-6
10 m/s² (f= 9…200 Hz) conforming to IEC 60068-2-6
|
Electromagnetic immunity
|
Immunity to electrostatic discharge - test level: 8 kV (contact discharge) conforming to IEC 61000-4-2
Immunity to electrostatic discharge - test level: 15 kV (air discharge) conforming to IEC 61000-4-2
Immunity to conducted RF disturbances - test level: 15 V/m (80 MHz...2 GHz) conforming to IEC 61000-4-3
Immunity to conducted RF disturbances - test level: 5 V/m (2...2.7 GHz) conforming to IEC 61000-4-3
Immunity to conducted RF disturbances - test level: 5 V/m (2.7...6 GHz) conforming to IEC 61000-4-3
Immunity to fast transients - test level: 4 kV (on input-output) conforming to IEC 61000-4-4
Surge immunity test - test level: 4 kV (between power supply and earth) conforming to IEC 61000-4-5
Surge immunity test - test level: 3 kV (between phases) conforming to IEC 61000-4-5
Immunity to conducted RF disturbances - test level: 15 V (0.15...80 MHz) conforming to IEC 61000-4-6
Immunity to magnetic fields - test level: 30 A/m (50...60 Hz) conforming to IEC 61000-4-8
Immunity to voltage dips conforming to IEC 61000-4-11
Disturbing field emission conforming to EN 55016-2-3
Limits for harmonic current emissions conforming to IEC 61000-3-2
Conforming to EN 55016-1-2
Conforming to EN 55016-2-1
|
Electromagnetic emission
|
Conducted emissions conforming to IEC 61000-6-3
Radiated emissions conforming to IEC 61000-6-4
|