|
|
|
ABLP1A24100
Regulated Power Supply, modicon power supply, 100...240V AC, 24V, 10A, single phase, Panel Mount
|
|
|
Main
Range of product
|
Modicon Power Supply
|
Product or component type
|
Power supply
|
Power supply type
|
Regulated switch mode
|
Variant option
|
Panel mount
|
Enclosure material
|
Aluminium
|
Nominal input voltage
|
100...240 V AC single phase
|
Rated power in W
|
240 W
|
Output voltage
|
24 V DC
|
Power supply output current
|
10 A
|
Complementary
Input voltage limits
|
85...264 V AC
|
Nominal network frequency
|
50…60 Hz
|
Network system compatibility
|
TN
TT
IT
|
Maximum leakage current
|
1 mA 240 V AC
|
Input protection type
|
Integrated fuse (not interchangeable) 6.3 A
|
Inrush current
|
35 A at 115 V
60 A at 230 V
|
Power factor
|
0.95 at 115 V AC
0.91 at 230 V AC
|
Efficiency
|
87 % at 230 V AC
|
Output voltage adjustment
|
21.6...26.4 V
|
Power dissipation in W
|
36 W
|
Current consumption
|
< 3.6 A 115 V AC
< 1.8 A 230 V AC
|
Turn-on time
|
< 1.2 s
|
Holding time
|
> 20 ms 115 V AC
> 40 ms 230 V AC
|
Startup with capacitive loads
|
8000 µF
|
Residual ripple
|
< 150 mV
|
Meantime between failure [MTBF]
|
700000 h at 25 °C, full load conforming to SR 332
|
Output protection type
|
Against overload and short-circuits, protection technology: automatic reset
Against over temperature, protection technology: manual reset
Against overvoltage, protection technology: manual reset
|
Connections - terminals
|
Screw connection: 0.75...2.5 mm², (AWG 18...AWG 14) without wire end ferrule
Screw connection: 0.75...1.5 mm², (AWG 18...AWG 16) with wire end ferrule
|
Line and load regulation
|
< 0.5 % at 0 to 100 % load at 25 °C
< 1 % at full voltage range in line at 25 °C
|
Status LED
|
1 LED (green) output voltage
|
Depth
|
190 mm
|
Height
|
50 mm
|
Width
|
93 mm
|
Net weight
|
0.85 kg
|
Output coupling
|
Parallel
Serial
|
Mounting support
|
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
Double-profile DIN rail
Panel mounting
|
Supply
|
SELV conforming to IEC 60950-1
SELV conforming to IEC 60204-1
SELV conforming to IEC 60364-4-41
|
Dielectric strength
|
3000 V AC with input to output
|
Service life
|
10 year(s)
|
Overvoltage category
|
II
|
Environment
Standards
|
IEC 62368-1
EN/IEC 61010-1
EN 61010-2-201
EN/IEC 61204-3
IEC 61000-6-1
IEC 61000-6-2
IEC 61000-6-3
IEC 61000-6-4
IEC 61000-3-2
EN 61000-3-3
UL 62368-1
UL 61010-1
UL 61010-2-201
CSA C22.2 No 62368-1
CSA C22.2 No 61010-1
CSA C22.2 No 61010-2-201
IEC 60335-1
EN/IEC 62368-1
|
Product certifications
|
CE
CULus
EAC
RCM
CB Scheme
KC
|
Operating altitude
|
5000 m
|
Shock resistance
|
150 m/s² for 11 ms
|
IP degree of protection
|
IP10
|
Ambient air temperature for operation
|
-10…50 °C without derating mounting position A, B, C, D, F, G < 2000 m
50…70 °C with current derating of 2.5 % per °C mounting position A, B, C, D, F, G < 2000 m
50…70 °C with current derating of 2.5 % per °C < 2000 m
|
Electrical shock protection class
|
Class I
|
Pollution degree
|
2
|
Vibration resistance
|
3 mm (f= 2…9 Hz) conforming to IEC 60068-2-6
10 m/s² (f= 9…200 Hz) conforming to IEC 60068-2-6
|
Electromagnetic immunity
|
Immunity to electrostatic discharge - test level: 8 kV (contact discharge) conforming to IEC 61000-4-2
Immunity to electrostatic discharge - test level: 15 kV (air discharge) conforming to IEC 61000-4-2
Immunity to conducted RF disturbances - test level: 15 V/m (80 MHz...2 GHz) conforming to IEC 61000-4-3
Immunity to conducted RF disturbances - test level: 5 V/m (2...2.7 GHz) conforming to IEC 61000-4-3
Immunity to conducted RF disturbances - test level: 5 V/m (2.7...6 GHz) conforming to IEC 61000-4-3
Immunity to fast transients - test level: 4 kV (on input-output) conforming to IEC 61000-4-4
Surge immunity test - test level: 4 kV (between power supply and earth) conforming to IEC 61000-4-5
Surge immunity test - test level: 3 kV (between phases) conforming to IEC 61000-4-5
Immunity to conducted RF disturbances - test level: 15 V (0.15...80 MHz) conforming to IEC 61000-4-6
Immunity to magnetic fields - test level: 30 A/m (50...60 Hz) conforming to IEC 61000-4-8
Immunity to voltage dips conforming to IEC 61000-4-11
Disturbing field emission conforming to EN 55016-2-3
Limits for harmonic current emissions conforming to IEC 61000-3-2
Conforming to EN 55016-1-2
Conforming to EN 55016-2-1
|
Electromagnetic emission
|
Conducted emissions conforming to IEC 61000-6-3
Radiated emissions conforming to IEC 61000-6-4
|
Packing Units
Unit Type of Package 1
|
PCE
|
Number of Units in Package 1
|
1
|
Package 1 Height
|
6.000 cm
|
Package 1 Width
|
14.000 cm
|
Package 1 Length
|
24.500 cm
|
Package 1 Weight
|
984.000 g
|
Unit Type of Package 2
|
S03
|
Number of Units in Package 2
|
9
|
Package 2 Height
|
30.000 cm
|
Package 2 Width
|
30.000 cm
|
Package 2 Length
|
40.000 cm
|
Package 2 Weight
|
9.269 kg
|
Unit Type of Package 3
|
P06
|
Number of Units in Package 3
|
72
|
Package 3 Height
|
75.000 cm
|
Package 3 Width
|
80.000 cm
|
Package 3 Length
|
60.000 cm
|
Package 3 Weight
|
82.152 kg
|
Offer Sustainability
Sustainable offer status
|
Green Premium product
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Pro-active compliance (Product out of EU RoHS legal scope)
|
Mercury free
|
Yes
|
RoHS exemption information
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
WEEE
|
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
California proposition 65
|
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
|
|
|