Range of product
|
Altistart U01 and TeSys U
|
Product or component type
|
Soft starter
|
Product destination
|
Asynchronous motors
|
Product specific application
|
Simple machine
|
Device short name
|
ATSU01
|
Network number of phases
|
3 phases
|
[Us] rated supply voltage
|
200...480 V - 10...10 %
|
Motor power kW
|
2.2 kW, 3 phases at 230 V
5.5 kW, 3 phases at 400 V
3 kW, 3 phases at 230 V
|
Motor power hp
|
3 hp, 3 phases at 230 V
7.5 hp, 3 phases at 460 V
|
IcL starter rating
|
12 A
|
Utilisation category
|
AC-53B conforming to EN/IEC 60947-4-2
|
Current consumption
|
65 mA
|
Type of start
|
Start with voltage ramp
|
Power dissipation in W
|
1.5 W at full load and at end of starting
121.5 W in transient state
|
Assembly style
|
With heat sink
|
Function available
|
Integrated bypass
|
Supply voltage limits
|
180…528 V
|
Supply frequency
|
50...60 Hz - 5...5 %
|
Network frequency
|
47.5...63 Hz
|
Output voltage
|
<= power supply voltage
|
[Uc] control circuit voltage
|
24 V DC +/- 10 %
|
Starting time
|
1 s / 100
5 s / 20
10 s / 10
Adjustable from 1 to 10 s
|
Deceleration time symb
|
Adjustable from 1 to 10 s
|
Starting torque
|
30...80 % of starting torque of motor connected directly on the line supply
|
Discrete input type
|
Logic (LI1, LI2, BOOST) stop, run and boost on start-up functions <= 8 mA 27 kOhm
|
Discrete input voltage
|
24...40 V
|
Input output isolation
|
Galvanic between power and control
|
Discrete input logic
|
Positive LI1, LI2, BOOST at State 0: < 5 V and <= 0.2 mA at State 1: > 13 V, >= 0.5 mA
|
Discrete output current
|
2 A DC-13
3 A AC-15
|
Discrete output type
|
Open collector logic LO1 end of starting signal
Relay outputs R1A, R1C NO
|
Discrete output voltage
|
24 V (voltage limits: 6...30 V) open collector logic
|
Minimum switching current
|
10 mA at 6 V DC for relay outputs
|
Maximum switching current
|
Relay outputs: 2 A at 30 V DC cos phi = 0.5 and L/R = 20 ms inductive load
Relay outputs: 2 A at 250 V AC AC-15 cos phi = 0.5 and L/R = 20 ms inductive load
|
Maximum switching voltage
|
440 V relay outputs
|
Display type
|
1 LED (green) for starter powered up
1 LED (yellow) for nominal voltage reached
|
Tightening torque
|
1.9…2.5 N.m
0.5 N.m
|
Electrical connection
|
4 mm screw clamp terminal - rigid 1 1...10 mm² AWG 8 power circuit
Screw connector - rigid without cable end 1 0.5...2.5 mm² AWG 14 control circuit
4 mm screw clamp terminal - rigid 2 1...6 mm² AWG 10 power circuit
Screw connector - rigid 2 0.5...1 mm² AWG 17 control circuit
Screw connector - flexible with cable end 1 0.5...1.5 mm² AWG 16 control circuit
4 mm screw clamp terminal - flexible without cable end 1 1.5...10 mm² AWG 8 power circuit
Screw connector - flexible without cable end 1 0.5...2.5 mm² AWG 14 control circuit
4 mm screw clamp terminal - flexible with cable end 2 1...6 mm² AWG 10 power circuit
4 mm screw clamp terminal - flexible without cable end 2 1.5...6 mm² AWG 10 power circuit
Screw connector - flexible without cable end 2 0.5...1.5 mm² AWG 16 control circuit
|
Marking
|
CE
|
Operating position
|
Vertical +/- 10 degree
|
Height
|
234 mm
|
Width
|
45 mm
|
Depth
|
150 mm
|
Net weight
|
0.34 kg
|
Motor power range AC-3
|
2.2…3 kW at 200…240 V 3 phases
4…6 kW at 380…440 V 3 phases
|
Motor starter type
|
Soft starter
|
Electromagnetic compatibility
|
Conducted and radiated emissions level B conforming to CISPR 11
Conducted and radiated emissions level B conforming to IEC 60947-4-2
Damped oscillating waves level 3 conforming to IEC 61000-4-12
Electrostatic discharge level 3 conforming to IEC 61000-4-2
EMC immunity conforming to EN 50082-1
EMC immunity level B conforming to EN 50082-2
Harmonics level 3 conforming to IEC 1000-3-2
Harmonics level 3 conforming to IEC 1000-3-4
Immunity to electrical transients level 4 conforming to IEC 61000-4-4
Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3
Voltage/current impulse level 3 conforming to IEC 61000-4-5
Conducted and radiated emissions level 3 conforming to IEC 61000-4-6
Immunity to conducted interference caused by radio-electrical fields level 4 conforming to IEC 61000-4-11
|
Standards
|
EN/IEC 60947-4-2
|
Product certifications
|
UL
CCC
C-Tick
CSA
|
IP degree of protection
|
IP20
|
Pollution degree
|
2 conforming to EN/IEC 60947-4-2
|
Vibration resistance
|
1 gn (f= 13…150 Hz) conforming to EN/IEC 60068-2-6
1.5 mm peak to peak (f= 3…13 Hz) conforming to EN/IEC 60068-2-6
|
Shock resistance
|
15 gn for 11 ms conforming to EN/IEC 60068-2-27
|
Relative humidity
|
5…95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
|
Ambient air temperature for operation
|
-10…40 °C (without derating)
40…50 °C (with current derating of 2 % per °C)
|
Ambient air temperature for storage
|
-25…70 °C conforming to EN/IEC 60947-4-2
|
Operating altitude
|
<= 1000 m without derating
> 1000 m with current derating of 2.2 % per additional 100 m
|