Characteristics
Main
Range of product Easy Altivar 610
Product or component type Variable speed drive
Product specific application Fan, pump, compressor, conveyor
Device short name ATV610
Variant Standard version
Product destination Asynchronous motors
Synchronous motors
Mounting mode Cabinet mount
EMC filter Integrated conforming to IEC 61800-3 category C3 with 50 m
IP degree of protection IP20
Type of cooling Forced convection
Supply frequency 50...60 Hz +/-5 %
Network number of phases 3 phases
[Us] rated supply voltage 380...460 V - 15...10 %
Motor power kW 110 kW for normal duty
90 kW for heavy duty
Motor power hp 150 hp for normal duty
125 hp for heavy duty
Line current 201 A at 380 V (normal duty)
175.7 A at 460 V (normal duty)
170 A at 380 V (heavy duty)
149.1 A at 460 V (heavy duty)
Prospective line Isc 50 kA
Apparent power 140.0 kVA at 460 V (normal duty)
118.8 kVA at 460 V (heavy duty)
Continuous output current 211 A at 2.5 kHz for normal duty
173 A at 2.5 kHz for heavy duty
Maximum transient current 232 A during 60 s (normal duty)
260 A during 60 s (heavy duty)
Asynchronous motor control profile Variable torque standard
Optimized torque mode
Constant torque standard
Output frequency 0.1…500 Hz
Nominal switching frequency 2.5 kHz
Switching frequency 1...8 kHz adjustable
Number of preset speeds 16 preset speeds
Communication port protocol Modbus serial
Option card Slot A: communication card, Profibus DP V1
Slot A: digital or analog I/O extension card
Slot A: relay output card
Complementary
Output voltage <= power supply voltage
Motor slip compensation Can be suppressed
Adjustable
Not available in permanent magnet motor law
Automatic whatever the load
Acceleration and deceleration ramps Linear adjustable separately from 0.01 to 9000 s
S, U or customized
Braking to standstill By DC injection
Protection type Thermal protection: motor
Motor phase break: motor
Thermal protection: drive
Overheating: drive
Overcurrent between output phases and earth: drive
Overload of output voltage: drive
Short-circuit protection: drive
Motor phase break: drive
Overvoltages on the DC bus: drive
Line supply overvoltage: drive
Line supply undervoltage: drive
Line supply phase loss: drive
Overspeed: drive
Break on the control circuit: drive
Frequency resolution Display unit: 0.1 Hz
Analog input: 0.012/50 Hz
Electrical connection Control, screw terminal: 0.5...1.5 mm²
Line side, screw terminal: 2 x 50...3 x 120 mm²
Motor, screw terminal: 3 x 50...3 x 120 mm²
Connector type 1 RJ45 (on the remote graphic terminal) for Modbus serial
Physical interface 2-wire RS 485 for Modbus serial
Transmission frame RTU for Modbus serial
Transmission rate 4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial
Type of polarization No impedance for Modbus serial
Number of addresses 1…247 for Modbus serial
Method of access Slave
Supply External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
Local signalling 2 LEDs for local diagnostic
1 LED (yellow) for embedded communication status
2 LEDs (dual colour) for communication module status
1 LED (red) for presence of voltage
Width 300 mm
Height 850 mm
1161 mm with IP21 conformity kit
Depth 375 mm
Net weight 85.5 kg
Analogue input number 3
Analogue input type AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 30 kOhm, resolution 12 bits
AI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits
AI2, AI3 software-configurable temperature probe or water level sensor
Discrete input number 6
Discrete input type DI1...DI6 programmable as logic input, 24 V DC (<= 30 V), impedance: 3.5 kOhm
DI5, DI6 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
Input compatibility DI1...DI6: logic input level 1 PLC conforming to IEC 61131-2
DI5, DI6: pulse input level 1 PLC conforming to IEC 65A-68
Discrete input logic Positive logic (source): DI1...DI6 configurable logic input, < 5 V (state 0), > 11 V (state 1)
Negative logic (sink): DI1...DI6 configurable logic input, > 16 V (state 0), < 10 V (state 1)
Positive logic (source): DI5, DI6 configurable pulse input, < 0.6 V (state 0), > 2.5 V (state 1)
Analogue output number 2
Analogue output type Software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bits
Software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits
Sampling duration 5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input
2 ms +/- 0.5 ms (DI1...DI6)configurable - discrete input
5 ms +/- 1 ms (DI5, DI6)configurable - pulse input
10 ms +/- 1 ms (AQ1, AQ2) - analog output
Accuracy +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
+/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output
Linearity error AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input
AQ1, AQ2: +/- 0.2 % for analog output
Relay output number 3
Relay output type Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles
Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles
Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles
Refresh time Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
Minimum switching current Relay output R1, R2, R3: 5 mA at 24 V DC
Maximum switching current Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
Isolation Between power and control terminals
Insulation resistance > 1 MOhm 500 V DC for 1 minute to earth
Environment
Noise level 76 dB conforming to 86/188/EEC
Power dissipation in W 2026 W(forced convection) at 380 V, switching frequency 2.5 kHz
Operating position Vertical +/- 10 degree
Electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Pollution degree 2 conforming to IEC 61800-5-1
Vibration resistance 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6
1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
Shock resistance 6 gn for 11 ms conforming to IEC 60068-2-27
Relative humidity 5…95 % without condensation conforming to IEC 60068-2-3
Ambient air temperature for operation -15…45 °C (without derating)
45…60 °C (with derating factor)
Operating altitude <= 1000 m without derating
1000...4800 m with current derating 1 % per 100 m
Environmental characteristic Chemical pollution resistance class 3C3 conforming to IEC 60721-3-3
Dust pollution resistance class 3S3 conforming to IEC 60721-3-3
Standards IEC 61800-3
Environment 2 category C3 IEC 61800-3
IEC 61800-5-1
IEC 60721-3
Marking CE
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 47.000 cm
Package 1 Width 67.000 cm
Package 1 Length 103.000 cm
Package 1 Weight 96.344 kg
Offer Sustainability
Packaging without single use plastic No
Packaging made with recycled cardboard No
REACh Regulation
print REACh Declaration
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free Yes
RoHS exemption information
print Yes
China RoHS Regulation
print China RoHS declaration
Environmental Disclosure
print Product Environmental Profile
Circularity Profile
print End of Life Information
WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Upgradeability Yes
Take-back No
Product contributes to saved and avoided emissions Yes
Carbon footprint (kg CO2 eq, Total Life cycle) 164855