BMEAHI0812H
analog isolated high level input module, Modicon X80, 8 HART inputs, 4 to 20mA, for severe environments
|
|
|
Main
Range of product
|
Modicon X80
|
Product or component type
|
Analog input module
|
Complementary
Application specific I/O
|
HART
|
Product compatibility
|
BMEP58... processor
BMXFTB20... terminal block
ABE7CPA31
ABE7CPA02
ABE7CPA03
Head module BMECRA31210
BMEXBP... backplane
|
Electrical connection
|
20 ways terminal block
Telefast
|
Isolation between channels
|
Isolated
|
Analogue input number
|
8
|
Analogue input type
|
Current 4...20 mA
|
Analogue input resolution
|
15 bits + sign
|
Input impedance
|
250 Ohm internally protective resistor (3.6 to 50 Ohm)
|
Measurement error
|
0.15 % of full scale 25 °C
0.55 % of full scale - 25...70 °C
|
Temperature drift
|
50 ppm/°C
|
Isolation voltage
|
1000 V DC for 60 s between channels
1400 V DC for 60 s between channels and ground
1400 V DC for 60 s between channels and bus
|
Checks
|
Broken wire detection
|
Topology
|
Point-to-point
|
Function available
|
I/O mapping
|
Net weight
|
0.233 kg
|
Environment
Ambient air temperature for operation
|
-25…70 °C
|
Ambient air temperature for storage
|
-40…85 °C
|
Operating altitude
|
0...2000 m
2000...5000 m with derating factor
|
Directives
|
2014/35/EU - low voltage directive
2014/30/EU - electromagnetic compatibility
2014/34/EU - ATEX directive
|
Product certifications
|
CE
UL
CSA
RCM
EAC
Merchant Navy
ATEX zone 2/22
IECEx zone 2/22
|
Standards
|
EN/IEC 61131-2
EN/IEC 61010-2-201
UL 61010-2-201
CSA C22.2 No 61010-2-201
IACS E10
EN/IEC 61000-6-5, interface type 1 and type 2
EN/IEC 61850-3, location G
EN/IEC 60079-0
|
Environmental characteristic
|
Gas resistant class Gx conforming to ISA S71.04
Gas resistant class 3C4 conforming to IEC 60721-3-3
Dust resistant class 3S4 conforming to IEC 60721-3-3
Sand resistant class 3S4 conforming to IEC 60721-3-3
Salt resistant level 2 conforming to IEC 68252
Mold growth resistant class 3B2 conforming to IEC 60721-3-3
Fungal spore resistant class 3B2 conforming to IEC 60721-3-3
Hazardous location class I division 2
|
Protective treatment
|
Conformal coating
|
Packing Units
Unit Type of Package 1
|
PCE
|
Number of Units in Package 1
|
1
|
Package 1 Height
|
5.500 cm
|
Package 1 Width
|
11.000 cm
|
Package 1 Length
|
12.000 cm
|
Package 1 Weight
|
239.000 g
|
Unit Type of Package 2
|
S02
|
Number of Units in Package 2
|
15
|
Package 2 Height
|
15.000 cm
|
Package 2 Width
|
30.000 cm
|
Package 2 Length
|
40.000 cm
|
Package 2 Weight
|
3.870 kg
|
Offer Sustainability
Packaging without single use plastic
|
Yes
|
Packaging made with recycled cardboard
|
Yes
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Pro-active compliance (Product out of EU RoHS legal scope)
|
Mercury free
|
Yes
|
RoHS exemption information
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
WEEE
|
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
California proposition 65
|
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
|
Take-back
|
No
|
Carbon footprint (kg.eq.CO2 per CR, Total Life cycle)
|
139
|
|
|