Primary voltage limit
|
85...264 V
|
Network frequency
|
50/60 Hz
|
Network frequency limits
|
47…63 Hz
|
Apparent power
|
0.13 kVA
|
Input current
|
0.55 A 240 V
1.01 A 115 V
|
Inrush current
|
30 A 120 V
60 A 240 V
|
I²t on activation
|
1 A².s 115 V
4 A².s 230 V
|
It on activation
|
0.1 A.s 115 V
0.15 A.s 230 V
|
MTBF reliability
|
792000 H
|
Protection type
|
Internal fuse not accessible for primary circuit
Overload protection for secondary circuit
Overvoltage protection for secondary circuit
Short-circuit protection for secondary circuit
|
Current at secondary voltage
|
5.5 A 3.3 V DC I/O module logic power supply
1.67 A 24 V DC I/O module power supply and processor
|
Maximum power dissipation in W
|
8.5 W
|
Status LED
|
1 LED (green) presence of voltages (OK)
1 LED (green) redundancy OK
1 LED (green) power supply status
|
Control type
|
RESET push-button cold restart
|
Electrical connection
|
1 connector 2 pin(s)alarm relay
1 connector 5 pin(s)line supply, protective earth
|
Insulation resistance
|
>= 100 MOhm primary/ground
>= 100 MOhm primary/secondary
|
Net weight
|
0.51 kg
|
Immunity to microbreaks
|
1 ms
|
Dielectric strength
|
1500 V primary/secondary I/O module logic power supply
1500 V primary/secondary I/O module power supply and processor
2300 V primary/secondary sensor power supply
1500 V primary/ground
500 V 24 V sensor output/ground
|
Vibration resistance
|
3 gn
|
Shock resistance
|
30 gn
|
IP degree of protection
|
IP20
|
Directives
|
2014/35/EU - low voltage directive
2014/30/EU - electromagnetic compatibility
|
Environmental characteristic
|
3C3 conforming to EN/IEC 60721-3-3
3C4 conforming to EN/IEC 60721-3-3
|
Ambient air temperature for storage
|
-40…85 °C
|
Ambient air temperature for operation
|
0…60 °C
|
Relative humidity
|
5…95 % at 55 °C without condensation
|
Protective treatment
|
TC
Conformal coating Humiseal 1A33
|
Operating altitude
|
0...2000 m
2000...5000 m with derating factor
|