Input compatibility
|
With 2-wire/3-wire proximity sensors conforming to IEC 60947-5-2
With 2-wire/3-wire proximity sensors conforming to IEC 61131-2 Type 2
|
Network frequency
|
50/60 Hz
|
Network frequency limits
|
47…63 Hz
|
Sensor power supply
|
170...264 V
|
Current state 1 guaranteed
|
>= 6 mA
|
Current state 0 guaranteed
|
<= 4 mA
|
Input impedance
|
21000 Ohm
|
Insulation resistance
|
> 10 MOhm 500 V DC
|
Power dissipation in W
|
4.73 W
|
AC activation response time
|
10 ms
|
AC deactivation response time
|
20 ms
|
Typical current consumption
|
76 mA at 3.3 V DC
93.6 mA at 24 V DC
|
Current consumption
|
<= 126 mA at 3.3 V DC
<= 154.8 mA at 24 V DC
|
MTBF reliability
|
1700000 H
|
Protection type
|
1 external fuse per group of channel0.5 A fast blow
|
Voltage detection threshold
|
> 164 V AC sensor OK
< 80 V AC sensor fault
|
Status LED
|
1 LED (green) module operating (RUN)
1 LED per channel (green) channel diagnostic
1 LED (red) module error (ERR)
1 LED (red) module I/O
|
Product weight
|
0.12 kg
|
Packaging without single use plastic
|
Yes
|
Packaging made with recycled cardboard
|
Yes
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Pro-active compliance (Product out of EU RoHS legal scope)
|
Mercury free
|
Yes
|
RoHS exemption information
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
WEEE
|
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
California proposition 65
|
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
|
Take-back
|
No
|
Carbon footprint (kg CO2 eq, Total Life cycle)
|
33
|