Input compatibility
|
With 2-wire/3-wire proximity sensors conforming to IEC 60947-5-2
With 2-wire/3-wire proximity sensors conforming to IEC 61131-2 type 3
|
Sensor power supply
|
19...30 V 60 °C
21.1...29.0 V 70 °C
|
Current state 1 guaranteed
|
>= 2 mA
|
Current state 0 guaranteed
|
<= 1.5 mA
|
Input impedance
|
6800 Ohm
|
Insulation resistance
|
> 10 MOhm 500 V DC
|
Power dissipation in W
|
3.1 W
|
DC typical response time
|
4 ms
|
DC maximum response time
|
7 ms
|
Response time on output
|
<= 8 ms deactivation
<= 10 ms activation
|
Paralleling of inputs
|
No
|
Typical current consumption
|
79 mA at 3.3 V DC
|
MTBF reliability
|
940000 H
|
Protection type
|
1 external fuse per group of input channel0.5 A fast blow
Reverse polarity protection on input
1 external fuse per output channel or group of output channel fast blow
|
Voltage detection threshold
|
< 14 V DC sensor fault
> 18 V DC sensor OK
|
Minimum switching current
|
1 mA 5 V DC
|
Maximum switching voltage
|
125 V DC
264 V AC
|
Mechanical durability
|
20000000 cycles
|
Electrical durability
|
AC-14: 100000 cycles at 120 VA 240 V at 70 °C (load factor 0.7)
AC-14: 100000 cycles at 150 VA 200 V at 70 °C (load factor 0.7)
AC-14: 100000 cycles at 240 VA 240 V at -25…60 °C (load factor 0.7)
AC-14: 100000 cycles at 300 VA 200 V at -25…60 °C (load factor 0.7)
AC-15: 100000 cycles at 100 VA 200 V at 70 °C (load factor 0.35)
AC-15: 100000 cycles at 120 VA 240 V at -25…60 °C (load factor 0.35)
AC-15: 100000 cycles at 200 VA 200 V at -25…60 °C (load factor 0.35)
AC-15: 100000 cycles at 60 VA 240 V at 70 °C (load factor 0.35)
DC-13: 100000 cycles at 12 W 24 V at 70 °C
DC-13: 100000 cycles at 24 W 24 V at -25…60 °C
AC-14: 300000 cycles at 36 VA 240 V at 70 °C (load factor 0.7)
AC-14: 300000 cycles at 40 VA 200 V at 70 °C (load factor 0.7)
AC-14: 300000 cycles at 72 VA 240 V at -25…60 °C (load factor 0.7)
AC-14: 300000 cycles at 80 VA 200 V at -25…60 °C (load factor 0.7)
AC-15: 300000 cycles at 18 VA 240 V at 70 °C (load factor 0.35)
AC-15: 300000 cycles at 30 VA 200 V at 70 °C (load factor 0.35)
AC-15: 300000 cycles at 36 VA 240 V at -25…60 °C (load factor 0.35)
AC-15: 300000 cycles at 60 VA 200 V at -25…60 °C (load factor 0.35)
DC-13: 300000 cycles at 3.6 W 24 V at 70 °C
DC-13: 300000 cycles at 7.2 W 24 V at -25…60 °C
|
Switching frequency
|
1 Hz
|
Status LED
|
1 LED (green) module operating (RUN)
1 LED per channel (green) channel diagnostic
1 LED (red) module error (ERR)
1 LED (red) module I/O
|
Product weight
|
0.135 kg
|
IP degree of protection
|
IP20
|
Directives
|
2014/35/EU - low voltage directive
2014/30/EU - electromagnetic compatibility
|
Environmental characteristic
|
Gas resistant class Gx
Gas resistant class 3C4
Dust resistant class 3S4
Sand resistant class 3S4
Salt resistant level 2
Mold growth resistant class 3B2
Fungal spore resistant class 3B2
|
Dielectric strength
|
1500 V AC at 50/60 Hz 1 minute, primary/secondary
2830 V AC at 50/60 Hz 1 minute, output relay
500 V DC 1 minute, between group of I/O
|
Vibration resistance
|
3 gn
|
Shock resistance
|
30 gn
|
Ambient air temperature for storage
|
-40…85 °C
|
Ambient air temperature for operation
|
-25…70 °C
|
Relative humidity
|
5…95 % at 55 °C without condensation
|
Protective treatment
|
Conformal coating
|
Operating altitude
|
0...2000 m
2000...5000 m with derating factor
|
Packaging without single use plastic
|
Yes
|
Packaging made with recycled cardboard
|
Yes
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Pro-active compliance (Product out of EU RoHS legal scope)
|
Mercury free
|
Yes
|
RoHS exemption information
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
WEEE
|
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
California proposition 65
|
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
|
Take-back
|
No
|
Carbon footprint (kg CO2 eq, Total Life cycle)
|
35
|