[Ith] conventional free air thermal current
|
3 A
|
Insulation resistance
|
> 10 MOhm 500 V DC
|
Power dissipation in W
|
2.7 W
|
Response time on output
|
< 10 ms activation
< 8 ms deactivation
|
Typical current consumption
|
79 mA at 3.3 V DC
|
MTBF reliability
|
2119902 H
|
Output overload protection
|
Use 1 fast blow fuse per channel or group of channel
|
Output overvoltage protection
|
Use discharge diode on each output DC
Use RC circuit on each output AC
Use ZNO surge limiter on each output AC
|
Output short-circuit protection
|
Use 1 fast blow fuse per channel or group of channel
|
Minimum switching current
|
10 mA 5 V DC
|
Electrical durability
|
AC-15: 100000 cycles at 220 VA 200...240 V (load factor 0.35)
AC-12: 1000000 cycles at 110 VA 110...120 V
AC-12: 1000000 cycles at 220 VA 200...240 V
AC-12: 1000000 cycles at 50 VA 48 V
AC-15: 1000000 cycles at 110 VA 200...240 V (load factor 0.35)
DC-12: 1000000 cycles at 24 W 24 V
DC-13: 1000000 cycles at 24 W 24 V
AC-15: 10000000 cycles at 10 VA 110...120 V (load factor 0.35)
AC-15: 10000000 cycles at 10 VA 200...240 V (load factor 0.35)
AC-15: 150000 cycles at 110 VA 110...120 V (load factor 0.35)
AC-15: 1500000 cycles at 50 VA 110...120 V (load factor 0.35)
AC-15: 2000000 cycles at 24 VA 48 V (load factor 0.35)
DC-13: 2000000 cycles at 10 W 24 V
DC-12: 300000 cycles at 40 W 24 V
AC-15: 3000000 cycles at 50 VA 200...240 V (load factor 0.35)
AC-12: 500000 cycles at 110 VA 48 V
AC-12: 500000 cycles at 220 VA 110...120 V
AC-15: 5000000 cycles at 10 VA 48 V (load factor 0.35)
AC-15: 500000 cycles at 24 VA 24 V (load factor 0.35)
AC-12: 700000 cycles at 50 VA 24 V
|
Status LED
|
1 LED (green) module operating (RUN)
1 LED per channel (green) channel diagnostic
1 LED (red) module error (ERR)
1 LED (red) module I/O
|
Net weight
|