Range of product
|
EasyPact
|
Product or component type
|
Circuit breaker
|
Device short name
|
Easypact EZC100H
|
Circuit breaker name
|
Easypact EZC100H
|
Device application
|
Distribution
|
Poles description
|
1P
|
Protected poles description
|
1t
|
Network type
|
DC
AC
|
Network frequency
|
50/60 Hz
|
[In] rated current
|
30 A at 40 °C
|
[Ui] rated insulation voltage
|
690 V AC 50/60 Hz conforming to IEC 60947-2
|
[Uimp] rated impulse withstand voltage
|
6 kV conforming to IEC 60947-2
|
[Ue] rated operational voltage
|
125 V DC conforming to IEC 60947-2
415 V AC 50/60 Hz conforming to IEC 60947-2
|
Breaking capacity code
|
H
|
Breaking capacity
|
10 kA Icu at 125 V DC 1P conforming to IEC 60947-2
25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
5 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2
|
[Ics] rated service breaking capacity
|
5 kA at 125 V DC conforming to IEC 60947-2
12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
|
Suitability for isolation
|
Yes conforming to IEC 60947-2
|
Utilisation category
|
Category A
|
Trip unit name
|
TM-D
|
Trip unit technology
|
Thermal-magnetic
|
Trip unit rating
|
30 A at 50 °C
|
Protection type
|
Short-circuit protection
Overload protection
|
Pollution degree
|
3 conforming to IEC 60664-1
3 conforming to IEC 947-1
|