Range of product
|
EasyPact
|
Product or component type
|
Circuit breaker
|
Device short name
|
Easypact EZC250N
|
Circuit breaker name
|
Easypact EZC250N
|
Device application
|
Distribution
|
Poles description
|
4P
|
Protected poles description
|
3t
|
Network type
|
AC
DC
|
Network frequency
|
50/60 Hz
|
[In] rated current
|
150 A at 40 °C
|
[Ui] rated insulation voltage
|
690 V AC 50/60 Hz conforming to IEC 60947-2
|
[Uimp] rated impulse withstand voltage
|
6 kV conforming to IEC 60947-2
|
[Ue] rated operational voltage
|
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2
|
Breaking capacity code
|
N
|
Breaking capacity
|
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 125 V DC 1P conforming to IEC 60947-2
20 kA Icu at 250 V DC 2P conforming to IEC 60947-2
8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
|
[Ics] rated service breaking capacity
|
10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 125 V DC conforming to IEC 60947-2
10 kA at 250 V DC conforming to IEC 60947-2
4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
|
Suitability for isolation
|
Yes conforming to IEC 60947-2
|
Utilisation category
|
Category A
|
Trip unit name
|
TM-D
|
Trip unit technology
|
Thermal-magnetic
|
Trip unit rating
|
150 A at 50 °C
|
Protection type
|
Overload protection
Short-circuit protection
|
Pollution degree
|
3 conforming to IEC 60947
|