Range of product
|
EasyPact
|
Product or component type
|
Circuit breaker
|
Device short name
|
Easypact EZC630N
|
Circuit breaker name
|
Easypact EZC630N
|
Device application
|
Distribution
|
Poles description
|
4P
|
Protected poles description
|
3t
|
Network type
|
AC
DC
|
Network frequency
|
50/60 Hz
|
[In] rated current
|
630 A at 40 °C
|
[Ui] rated insulation voltage
|
690 V AC 50/60 Hz conforming to IEC 60947-2
|
[Uimp] rated impulse withstand voltage
|
6 kV conforming to IEC 60947-2
|
[Ue] rated operational voltage
|
250 V DC conforming to IEC 60947-2
440 V AC 50/60 Hz conforming to IEC 60947-2
|
Breaking capacity code
|
N
|
Breaking capacity
|
36 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
40 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2
36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
36 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
|
[Ics] rated service breaking capacity
|
18 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
40 kA at 220/230 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
|
Suitability for isolation
|
Yes conforming to IEC 60947-2
|
Utilisation category
|
Category A
|
Trip unit name
|
TM-D
|
Trip unit technology
|
Thermal-magnetic
|
Trip unit rating
|
500 A at 50 °C
|
Protection type
|
Short-circuit protection
Overload protection
|
Pollution degree
|
3 conforming to IEC 60947
|