Utilisation category
|
AC-7A
|
Poles description
|
4P
|
Power pole contact composition
|
4 NO
|
[Ue] rated operational voltage
|
<= 250 V AC
|
[Ie] rated operational current
|
100 A AC-7A
|
Operating position
|
30°/vertical
|
Control circuit type
|
AC at 50 Hz
|
[Uc] control circuit voltage
|
220...240 V AC 50 Hz
|
[Uimp] rated impulse withstand voltage
|
4 kV
|
[Ith] conventional free air thermal current
|
100 A (at 50 °C) for power circuit
|
[Icw] rated short-time withstand current
|
800 A 40 °C - 10 s for power circuit
250 A 40 °C - 30 s for power circuit
|
Associated fuse rating
|
100 A gL at <= 440 V for power circuit
|
Average impedance
|
1 mOhm - Ith 100 A 50 Hz for power circuit
|
[Ui] rated insulation voltage
|
500 V conforming to IEC 61095
500 V conforming to VDE 0110
|
Electrical durability
|
AC-7A: 30000 cycles
|
Power dissipation per pole
|
10 W
|
Control type
|
Remote control
|
Mounting mode
|
Clip-on
|
Mounting support
|
DIN rail
|
Standards
|
IEC 60947-5
IEC 61095
|
Connections - terminals
|
Power circuit: screw clamp terminals 1 cable(s) 35 mm²flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 35 mm²flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 35 mm²solid without cable end
Power circuit: screw clamp terminals 2 cable(s) 10 mm²solid without cable end
Control circuit: screw clamp terminals 1 cable(s) 2.5 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 2.5 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1.5 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1.5 mm²solid without cable end
|
Tightening torque
|
Control circuit: 0.8 N.m - on screw clamp terminals
Power circuit: 3.5 N.m - on screw clamp terminals
|
Operating time
|
10...25 ms opening
10...30 ms closing
|
Mechanical durability
|
1000000 cycles
|
Maximum operating rate
|
300 cyc/h 50 °C
|
Control circuit voltage limits
|
Drop-out: 0.2...0.75 Uc at 50 Hz (at <50 °C)
Operational: 0.85...1.1 Uc at 50 Hz (at <50 °C)
|
Inrush power in VA
|
106 VA 50 Hz (at 20 °C)
|
Hold-in power consumption in VA
|
13 VA 50 Hz (at 20 °C)
|
Heat dissipation
|
4.2 W at 50/60 Hz
|