GV7AS055
Voltage release, TeSys GV5 GV6 GV7, MX shunt trip, 48V AC 50/60Hz
|
|
|
|
|
End of Commercialization DEC 09, 2020
|
|
|
|
|
Main
Range
|
TeSys
|
Product or component type
|
Shunt trip
|
Device short name
|
GV7AS
|
Device application
|
Control
|
Range compatibility
|
TeSys TeSys GV5
TeSys TeSys GV6
TeSys TeSys GV7
|
Complementary
[Uc] control circuit voltage
|
48 V AC 50/60 Hz
|
Control circuit voltage limits
|
0.7...1.1 Un
|
[Ui] rated insulation voltage
|
690 V AC conforming to IEC 60947-1
600 V AC conforming to UL 508
600 V AC conforming to CSA C22.2 No 14
|
Threshold tripping voltage
|
0.2...0.75 Ue
|
Inrush power in VA
|
10 VA AC
|
Hold-in power consumption in VA
|
5 VA AC
|
Operating time
|
< 50 ms conforming to IEC 60947-1
|
On-load factor
|
100 %
|
Connections - terminals
|
Screw clamp terminals 1 cable(s) 1 mm²flexible with cable end
Screw clamp terminals 1 cable(s) 1.5 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 1.5 mm²solid
|
Tightening torque
|
1.2 N.m on screw clamp terminals
|
Net weight
|
0.11 kg
|
Quantity per set
|
Set of 10
|
Offer Sustainability
REACh free of SVHC
|
Yes
|
EU RoHS Directive
|
Compliant
EU RoHS Declaration
|
Toxic heavy metal free
|
Yes
|
Mercury free
|
Yes
|
RoHS exemption information
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
WEEE
|
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
California proposition 65
|
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
|