[Ui] rated insulation voltage
|
690 V conforming to IEC 60947-1
300 V conforming to UL 508
300 V conforming to CSA C22.2 No 14
|
[Ue] rated operational voltage
|
48...690 V AC
24...240 V DC
|
[Ith] conventional free air thermal current
|
6 A
2.5 A for fault signalling
|
Mechanical durability
|
100000 cycles
|
Minimum switching current
|
5 mA
|
Minimum switching voltage
|
17 V
|
Protection type
|
GB2CB... circuit breaker
GG fuse 10 A
|
Rated operational power in VA
|
300 VA at 48 V AC-15 - electrical durability: 100000 cycles
414 VA at 690 V AC-15 - electrical durability: 100000 cycles
500 VA at 110…127 V AC-15 - electrical durability: 100000 cycles
500 VA at 500 V AC-15 - electrical durability: 100000 cycles
650 VA at 440 V AC-15 - electrical durability: 100000 cycles
720 VA at 230…240 V AC-15 - electrical durability: 100000 cycles
850 VA at 380…415 V AC-15 - electrical durability: 100000 cycles
36 VA at 24 V AC-14 - electrical durability: 1000 cycles
48 VA at 48 V AC-14 - electrical durability: 1000 cycles
72 VA at 110…127 V AC-14 - electrical durability: 1000 cycles
|
Rated operational power in W
|
120 W at 240 V DC-13 - electrical durability: 100000 cycles
140 W at 110 V DC-13 - electrical durability: 100000 cycles
140 W at 24 V DC-13 - electrical durability: 100000 cycles
180 W at 60 V DC-13 - electrical durability: 100000 cycles
240 W at 48 V DC-13 - electrical durability: 100000 cycles
15 W at 48 V DC-13 - electrical durability: 1000 cycles
24 W at 24 V DC-13 - electrical durability: 1000 cycles
9 W at 60 V DC-13 - electrical durability: 1000 cycles
|
Tightening torque
|
1.4 N.m - on screw clamp terminals
|
Height
|
89 mm
|
Width
|
9.3 mm
|
Depth
|
66 mm
|
Net weight
|
0.055 kg
|
Colour
|
Dark grey
|