Range compatibility
|
TeSys GV2ME
TeSys Deca
|
[Uc] control circuit voltage
|
220...240 V AC 50 Hz
|
Control circuit voltage limits
|
0.85...1.1 Un
|
[Ui] rated insulation voltage
|
690 V AC conforming to IEC 60947-1
600 V AC conforming to UL 60947-4-1
600 V AC conforming to CSA C22.2 No 60947-4-1
|
Threshold tripping voltage
|
0.7...0.35 Un
|
Inrush power in VA
|
12 VA AC
|
Inrush power in W
|
8 W
|
Hold-in power consumption in VA
|
3.5 VA AC
|
Hold-in power consumption in W
|
1.1 W
|
Operating time
|
10...15 ms conforming to IEC 60947-1
|
On-load factor
|
100 %
|
Connections - terminals
|
Screw clamp terminals 1 cable(s) 1…2.5 mm²solid
Screw clamp terminals 2 cable(s) 1…2.5 mm²solid
Screw clamp terminals 1 cable(s) 0.75…2.5 mm²flexible without cable end
Screw clamp terminals 2 cable(s) 0.75…2.5 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 0.75…1.5 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 0.75…1.5 mm²flexible with cable end
|
Tightening torque
|
< 1.4 N.m on screw clamp terminals
|
Mechanical durability
|
30000 cycles
|
Quantity per set
|
Set of 10
|
Height
|
89 mm
|
Width
|
18 mm
|
Depth
|
66 mm
|
Net weight
|
0.105 kg
|
Colour
|
Dark grey
|