Poles description
|
3P
|
Network type
|
AC
|
Utilisation category
|
AC-3
|
Network frequency
|
50/60 Hz conforming to IEC 60947-2
|
Mounting mode
|
By clips
By screws
|
Mounting support
|
Rail
|
Mounting position
|
Any position
|
Motor power kW
|
4 kW at 230 V AC 50/60 Hz
7.5 kW at 400 V AC 50/60 Hz
9 kW at 440 V AC 50/60 Hz
10 kW at 500 V AC 50/60 Hz
15 kW at 690 V AC 50/60 Hz
|
Breaking capacity
|
Icu: >= 100 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
Icu: 2 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2
Icu: 10 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Icu: 6 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Icu: 5 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
|
[Ics] rated service short-circuit breaking capacity
|
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
|
Control type
|
Push-button
|
Thermal protection adjustment range
|
13…18 A
|
Magnetic tripping current
|
223 A
|
[Ue] rated operational voltage
|
690 V AC 50/60 Hz conforming to IEC 60947-2
|
[Ui] rated insulation voltage
|
690 V AC 50/60 Hz conforming to IEC 60947-2
|
[Uimp] rated impulse withstand voltage
|
6 kV conforming to IEC 60947-2
|
Power dissipation
|
2.5 W (per pole)
|
Mechanical durability
|
100000 cycles
|
Electrical durability
|
100000 cycles for AC-3
|
Maximum operating rate
|
25 cyc/h
|
Connections - terminals
|
Screw clamp terminals 2 1…6 mm² - cable stiffness: solid
Screw clamp terminals 2 1.5…6 mm² - cable stiffness: flexible without cable end
Screw clamp terminals 2 1…4 mm² - cable stiffness: flexible with cable end
|
Height
|
89 mm
|
Width
|
44.5 mm
|
Depth
|
78 mm
|
Net weight
|
0.26 kg
|