HMIG2U
base unit, Harmony GTU, standard box, 1GB built-in flash memory
|
|
|
Main
Range of product
|
Harmony GTU
|
Product or component type
|
Base unit
|
Device short name
|
standard box
|
Range compatibility
|
Harmony GTU
Allen-Bradley
ABB
MitsubishI
Omron
Siemens
|
[Us] rated supply voltage
|
12...24 V DC power supply
|
Complementary
Integrated connection type
|
Ethernet TCP/IP with 2 RJ45
COM1 serial link SUB-D 9 RS232C, transmission rate: 2400...115200 bps
COM2 serial link RJ45 RS485, transmission rate: 187.5 kbps
USB 2.0 port with 2 USB type A
USB 2.0 port mini B USB
|
Communication port protocol
|
Modbus
Modbus TCP/IP
Uni-Telway
|
Operating system
|
Harmony
|
Software package
|
Vijeo Designer run time 8000 variables
|
Processor name
|
CPU RISC 600 MHz
|
Data storage equipment
|
1 GB built-in flash memory
|
Port Ethernet
|
10BASE-T/100BASE-T
|
Memory description
|
256 MB RAM internal (2 x 13 mm board)
512 KB NVRAM backup memory
|
Number of slots
|
1 slot(s) for SD card
|
Realtime clock
|
Built-in
|
Local signalling
|
LED: (steady), green for operating status (RUN)
LED: (faded), green for stand-by
LED: (flashing), orange for software starting up
LED: (steady), red for power ON
LED: (alternate), green, orange and red for module error (ERR)
LED: (alternate), red/orange for boot status
LED: (alternate), green/red for connection status
|
Type of cooling
|
Natural convection
|
Width
|
188 mm
|
Height
|
131 mm
|
Depth
|
45 mm
|
Product weight
|
0.9 kg
|
Environment
Standards
|
CSA C22.2 No 142
ANSI/ISA 12-12-01
UL 508
Class I division 2 CSA C22.2 No 213
IEC 61132-2
|
Product certifications
|
CE
CULus
ATEX
IEC-Ex
RCM
GL
KC
CUL
EAC
UKCA
UKEX
|
Resistance to fast transients
|
1 kV (signal ports) conforming to IEC 61000-4-4
2 kV (power ports) conforming to IEC 61000-4-4
|
Resistance to electrostatic discharge
|
6 kV contact discharge conforming to IEC 61000-4-2 level 3
8 kV air discharge conforming to IEC 61000-4-2 level 3
|
Ambient air temperature for operation
|
0…60 °C
|
Ambient air temperature for storage
|
-20…60 °C
|
Pollution degree
|
2 conforming to IEC 61131-2 ed.3
|
Environmental characteristic
|
Corrosive gas free
|
Relative humidity
|
10…90 % non-condensing
|
Operating altitude
|
2000 m
|
Vibration resistance
|
3.5 mm constant amplitude (f = 5…9 Hz) X, Y, Z directions for 10 cycles (approx. 100 min) conforming to IEC 61131-2
9.8 m/s² (f = 9…150 Hz) X, Y, Z directions for 10 cycles (approx. 100 min) conforming to IEC 61131-2
|
Shock resistance
|
147 m/s² (X, Y, Z directions for 3 times) conforming to IEC 61131-2
|
Electromagnetic compatibility
|
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
|
Packing Units
Unit Type of Package 1
|
PCE
|
Number of Units in Package 1
|
1
|
Package 1 Height
|
14.500 cm
|
Package 1 Width
|
21.500 cm
|
Package 1 Length
|
26.500 cm
|
Package 1 Weight
|
1.167 kg
|
Unit Type of Package 2
|
S04
|
Number of Units in Package 2
|
4
|
Package 2 Height
|
30.000 cm
|
Package 2 Width
|
40.000 cm
|
Package 2 Length
|
60.000 cm
|
Package 2 Weight
|
5.731 kg
|
Offer Sustainability
Sustainable offer status
|
Green Premium product
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Pro-active compliance (Product out of EU RoHS legal scope)
|
Mercury free
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
RoHS exemption information
|
Yes
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
California proposition 65
|