Schneider-Electric
 
HMISTW6600 picture- web-product-data-sheet
HMISTW6600
touch panel screen, Harmony ST6, 12inch wide display, 2Ethernet, USB host and device, 24V DC
Schneider Electric
Characteristics
Main
Range of product Harmony ST6
Product or component type Touch panel screen
Software designation Web interface for operator
Processor name ARM Cortex-A8
Processor frequency 800 MHz
Memory description 512 MB device memory
512 MB backup memory
128 kB user data memory
Complementary
Display size 12 inch
Display type Colour TFT LCD
Display colour 16 million colours
Display resolution 1280 x 800 pixels WXGA
Touch panel Single touch analogue resistive
Backlight lifespan 50000 hours with white
Brightness 16 levels
Character font ASCII
ASCII (European characters)
Katakana
[Us] rated supply voltage 24 V DC (+/- 20 %)
Power consumption in W 18.4 W
Inrush current 30 A
Local signalling Status LED green, steady for offline
Status LED green, steady for operating
Status LED green, flashing for operating
Status LED green, faded for stand-by
Status LED orange, flashing for software starting up
Status LED red, steady for power supply (ON)
Status LED red, flashing for operating
Status LED red, off for power supply (OFF)
Port Ethernet 10/100BASE
Integrated connection type 1 USB 2.0 type Aback
1 Ethernet - female RJ45bottom
Supply External supply
Realtime clock Built-in 0...50 °C
Built-in 10...90 % RH
Fixing mode By 4 screws, mounting on 1.6...5 mm thick panel conforming to UL 61010-2-201
By 4 screws conforming to IEC 61131-2
By 4 screws conforming to IEC 61000-6-2
Enclosure material PC
Front material Aluminium
Marking CE
Cut-out dimensions 295 x 217 mm panel cut dimension
Height 235 mm
Width 313 mm
Depth 50 mm
Product weight 1.8 kg
Environment
Immunity to microbreaks 10 ms
Standards IEC 61000-6-4
IEC 61000-6-2
IEC 61131-2
UL 61010-2-201
CSA C22.2 No 61010-2-201
Product certifications CSA
CE
UKCA
Directives 2014/35/EU - low voltage directive
2014/30/EU - electromagnetic compatibility
Ambient air temperature for operation 0…50 °C
Ambient air temperature for storage -20…60 °C
Relative humidity 10…90 % non-condensing
Operating altitude 2000 m
IP degree of protection IP20 (rear panel) conforming to IEC 61131-2
IP65 (front panel) conforming to IEC 61131-2
NEMA degree of protection NEMA 4 front panel (indoor use)
NEMA 13 front panel (in enclosure)
Shock resistance 147 m/s² for 11 ms (X, Y, Z directions for 3 times) conforming to IEC 61131-2
Vibration resistance +/- 3.5 mm (f = 5…9 Hz) X, Y, Z directions for 10 cycles (approx. 100 min) conforming to IEC 61131-2
9.8 m/s² (f = 9…150 Hz)
Electromagnetic compatibility Electrical fast transient/burst immunity test - test level: 2 kV (power ports) conforming to IEC 61000-4-4
Electrical fast transient/burst immunity test - test level: 1 kV (signal ports)
Electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to IEC 61000-4-2 level 3
Electrostatic discharge immunity test - test level: 8 kV (air discharge)
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 12.95 cm
Package 1 Width 30.73 cm
Package 1 Length 40.39 cm
Package 1 Weight 2.31 kg
Unit Type of Package 2 CAR
Number of Units in Package 2 4
Package 2 Height 34 cm
Package 2 Width 41 cm
Package 2 Length 54 cm
Package 2 Weight 10.334 kg
Unit Type of Package 3 P12
Number of Units in Package 3 16
Package 3 Height 48.5 cm
Package 3 Width 80 cm
Package 3 Length 120 cm
Package 3 Weight 53.336 kg
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation
print REACh Declaration
EU RoHS Directive Compliant with Exemptions
Mercury free Yes
China RoHS Regulation
print China RoHS declaration
RoHS exemption information
print Yes
Environmental Disclosure
print Product Environmental Profile
WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov