Range compatibility
|
EasyPact EasyPact TVS LC1E
|
Mounting location
|
Front
|
Auxiliary contacts operation
|
Instantaneous
|
Pole contact composition
|
2 NC
|
[Ui] rated insulation voltage
|
690 V - for control circuit conforming to IEC 60947-5-1
|
[Ue] rated operational voltage
|
<= 690 V
|
[Ith] conventional free air thermal current
|
8 A (at 60 °C)
|
Irms rated making capacity
|
140 A AC conforming to IEC 60947-5-1
|
[Icw] rated short-time withstand current
|
100 A - 1 s
120 A - 500 ms
140 A - 100 ms
|
Protection type
|
GG fuse 10 A
|
Mechanical durability
|
10 Mcycles
|
Minimum switching current
|
5 mA
|
Minimum switching voltage
|
17 V
|
Non-overlap time
|
1.5 ms on energisation no overlap between NC and NO contact
1.5 ms on de-energisation no overlap between NC and NO contact
|
Insulation resistance
|
> 10 MOhm
|
Connections - terminals
|
Control circuit: screw clamp terminals 1 1 mm² - external diameter: 6 mm - cable stiffness: solid or flexible with cable end
Control circuit: screw clamp terminals 1 1 mm² - external diameter: 6 mm - cable stiffness: solid or flexible without cable end
Control circuit: screw clamp terminals 2 2.5 mm² - external diameter: 6 mm - cable stiffness: solid or flexible with cable end
Control circuit: screw clamp terminals 2 2.5 mm² - external diameter: 6 mm - cable stiffness: solid or flexible without cable end
|
Net weight
|
0.035 kg
|