This Application will be decommissioned as of January 7th 2025

LC1F1154 |
Schneider-Electric
 
LC1F1154 picture- web-product-data-sheet
LC1F1154
Contactor body, TeSys F, 4P(4NO), AC-1, <=440V 200A, without coil
Schneider Electric
Characteristics
Main
Range TeSys
Product name TeSys F
Product or component type Contactor
Device short name LC1F
Contactor application Resistive load
Utilisation category AC-1
Poles description 4P
Power pole contact composition 4 NO
[Ue] rated operational voltage <= 690 V AC 50/60 Hz
<= 460 V DC
[Ie] rated operational current 200 A (at <40 °C) at <= 440 V AC-1
Complementary
[Uc] control circuit voltage 24...575 V AC 40...400 Hz with LX9 coil
24...460 V DC with LX4 coil
100...250 V AC 50/60 Hz with LXE coil
100...380 V DC with LXE coil
[Uimp] rated impulse withstand voltage 8 kV
Overvoltage category III
[Ith] conventional free air thermal current 200 A (at 40 °C)
Irms rated making capacity 1150 A conforming to IEC 60947-4-1
Rated breaking capacity 920 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current 1100 A 40 °C - 10 s
640 A 40 °C - 30 s
520 A 40 °C - 1 min
400 A 40 °C - 3 min
320 A 40 °C - 10 min
Associated fuse rating 200 A gG at <= 440 V
Average impedance 0.37 mOhm - Ith 200 A 50 Hz
[Ui] rated insulation voltage 1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
Power dissipation per pole 15 W AC-1
Control circuit voltage limits Operational: 0.85...1.1 Uc AC 40...400 Hz with LX9 coil
Drop-out: 0.2...0.55 Uc AC 40...400 Hz with LX9 coil
Operational: 0.85...1.1 Uc DC with LX4 coil
Drop-out: 0.15...0.2 Uc DC with LX4 coil
Operational: 85...275 V AC 50/60 Hz with LXE coil
Drop-out: 0...60 V AC 50/60 Hz with LXE coil
Operational: 85...418 V DC with LXE coil
Drop-out: 0...45 V DC with LXE coil
Heat dissipation 5.9…7.2 W
2.2…5.5 W
Operating time 130 ms opening for with LX9 coil
30...40 ms closing for with LX4 coil
30...50 ms opening for with LX4 coil
40...80 ms closing for with LXE coil
6...54 ms opening for with LXE coil
Mounting support Plate
Standards EN 60947-4-1
IEC 60947-4-1
JIS C8201-4-1
EN 60947-1
IEC 60947-1
Product certifications CB
UL
RINA
DNV
LROS (Lloyds register of shipping)
RMRoS
CSA
ABS
BV
UKCA
Connections - terminals Power circuit: lugs-ring terminals 1 cable(s) 95 mm²
Power circuit: connector 1 cable(s) 95 mm²
Power circuit: bar 2 cable(s) - busbar cross section: 20 x 3 mm
Power circuit: bolted connection
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²
Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²flexible without cable end
Control circuit: screw clamp terminals 1.0 cable(s) 0.25…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²solid without cable end
Tightening torque Power circuit: 10 N.m
Control circuit: 1.2 N.m
Control circuit: 0.6 N.m
Inrush power in VA 590…855 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX9 coil
543…665 VA (at 20 °C)with LX4 coil
280…310 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil
270…320 VA (at 20 °C)with LXE coil
Hold-in power consumption in VA 6.6…8.1 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX9 coil
3.94…4.83 VA (at 20 °C)with LX4 coil
4.5…7.0 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil
2.5…4.0 VA (at 20 °C)with LXE coil
Maximum operating rate 2400 cyc/h 55 °C
Compatibility code LC1F
Environment
IP degree of protection IP2X front face with shrouds conforming to IEC 60529
IP2X front face with shrouds conforming to VDE 0106
Protective treatment TH
Ambient air temperature for operation -40…60 °C
Ambient air temperature for storage -60…80 °C
Permissible ambient air temperature around the device 60…70 °C at Uc
Operating altitude 3000 m without derating
Mechanical robustness Vibrations contactor open: 2 Gn, 5...300 Hz
Vibrations contactor closed: 6 Gn, 5...300 Hz
Shocks contactor open: 9 Gn for 1/2 sine wave (11 ms)
Shocks contactor closed: 15 Gn for 1/2 sine wave (11 ms)
Height 162 mm
Width 200.5 mm
Depth 171 mm
Net weight 3.83 kg
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 21.500 cm
Package 1 Width 20.000 cm
Package 1 Length 26.500 cm
Package 1 Weight 4.208 kg
Unit Type of Package 2 P06
Number of Units in Package 2 18
Package 2 Height 75.000 cm
Package 2 Width 60.000 cm
Package 2 Length 80.000 cm
Package 2 Weight 84.244 kg
Offer Sustainability
Packaging without single use plastic No
Packaging made with recycled cardboard No
SCIP Number Fd9a8828-e2ec-48b0-8cbe-cb8a9fd887e0
REACh Regulation
print REACh Declaration
EU RoHS Directive Compliant with Exemptions
Mercury free Yes
RoHS exemption information
print Yes
China RoHS Regulation
print China RoHS declaration
Environmental Disclosure
print Product Environmental Profile
Circularity Profile
print End of Life Information
WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Take-back No
Carbon footprint (kg.eq.CO2 per CR, Total Life cycle) 822
Contractual warranty
Warranty 18 months