[Uc] control circuit voltage
|
24...575 V AC 40...400 Hz with LX9 coil
24...460 V DC with LX4 coil
100...250 V AC 50/60 Hz with LXE coil
100...380 V DC with LXE coil
|
[Uimp] rated impulse withstand voltage
|
8 kV
|
Overvoltage category
|
III
|
[Ith] conventional free air thermal current
|
200 A (at 40 °C)
|
Irms rated making capacity
|
1150 A conforming to IEC 60947-4-1
|
Rated breaking capacity
|
920 A conforming to IEC 60947-4-1
|
[Icw] rated short-time withstand current
|
1100 A 40 °C - 10 s
640 A 40 °C - 30 s
520 A 40 °C - 1 min
400 A 40 °C - 3 min
320 A 40 °C - 10 min
|
Associated fuse rating
|
200 A gG at <= 440 V
|
Average impedance
|
0.37 mOhm - Ith 200 A 50 Hz
|
[Ui] rated insulation voltage
|
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
|
Power dissipation per pole
|
15 W AC-1
|
Control circuit voltage limits
|
Operational: 0.85...1.1 Uc AC 40...400 Hz with LX9 coil
Drop-out: 0.2...0.55 Uc AC 40...400 Hz with LX9 coil
Operational: 0.85...1.1 Uc DC with LX4 coil
Drop-out: 0.15...0.2 Uc DC with LX4 coil
Operational: 85...275 V AC 50/60 Hz with LXE coil
Drop-out: 0...60 V AC 50/60 Hz with LXE coil
Operational: 85...418 V DC with LXE coil
Drop-out: 0...45 V DC with LXE coil
|
Heat dissipation
|
5.9…7.2 W
2.2…5.5 W
|
Operating time
|
130 ms opening for with LX9 coil
30...40 ms closing for with LX4 coil
30...50 ms opening for with LX4 coil
40...80 ms closing for with LXE coil
6...54 ms opening for with LXE coil
|
Mounting support
|
Plate
|
Standards
|
EN 60947-4-1
IEC 60947-4-1
JIS C8201-4-1
EN 60947-1
IEC 60947-1
|
Product certifications
|
CB
UL
RINA
DNV
LROS (Lloyds register of shipping)
RMRoS
CSA
ABS
BV
UKCA
|
Connections - terminals
|
Power circuit: lugs-ring terminals 1 cable(s) 95 mm²
Power circuit: connector 1 cable(s) 95 mm²
Power circuit: bar 2 cable(s) - busbar cross section: 20 x 3 mm
Power circuit: bolted connection
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²
Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²flexible without cable end
Control circuit: screw clamp terminals 1.0 cable(s) 0.25…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²solid without cable end
|
Tightening torque
|
Power circuit: 10 N.m
Control circuit: 1.2 N.m
Control circuit: 0.6 N.m
|
Inrush power in VA
|
590…855 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX9 coil
543…665 VA (at 20 °C)with LX4 coil
280…310 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil
270…320 VA (at 20 °C)with LXE coil
|
Hold-in power consumption in VA
|
6.6…8.1 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX9 coil
3.94…4.83 VA (at 20 °C)with LX4 coil
4.5…7.0 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil
2.5…4.0 VA (at 20 °C)with LXE coil
|
Maximum operating rate
|
2400 cyc/h 55 °C
|
Compatibility code
|
LC1F
|
Packaging without single use plastic
|
No
|
Packaging made with recycled cardboard
|
No
|
SCIP Number
|
Fd9a8828-e2ec-48b0-8cbe-cb8a9fd887e0
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Compliant with Exemptions
|
Mercury free
|
Yes
|
RoHS exemption information
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
WEEE
|
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
California proposition 65
|
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
|
Take-back
|
No
|
Carbon footprint (kg.eq.CO2 per CR, Total Life cycle)
|
822
|