[Uc] control circuit voltage
|
24...575 V AC 40...400 Hz with LX1/LX9 coil
24...460 V DC with LX4 coil
100...250 V AC 50/60 Hz with LXE coil
100...380 V DC with LXE coil
|
[Uimp] rated impulse withstand voltage
|
8 kV
|
Overvoltage category
|
III
|
[Ith] conventional free air thermal current
|
250 A (at 40 °C)
|
Irms rated making capacity
|
1500 A conforming to IEC 60947-4-1
|
Rated breaking capacity
|
1200 A conforming to IEC 60947-4-1
|
[Icw] rated short-time withstand current
|
1200 A 40 °C - 10 s
700 A 40 °C - 30 s
600 A 40 °C - 1 min
450 A 40 °C - 3 min
350 A 40 °C - 10 min
|
Associated fuse rating
|
250 A gG at <= 440 V
|
Average impedance
|
0.35 mOhm - Ith 250 A 50 Hz
|
[Ui] rated insulation voltage
|
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
|
Power dissipation per pole
|
22 W AC-1
|
Control circuit voltage limits
|
Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil
Drop-out: 0.2...0.55 Uc AC 40...400 Hz with LX1/LX9 coil
Operational: 0.85...1.1 Uc DC with LX4 coil
Drop-out: 0.15...0.2 Uc DC with LX4 coil
Operational: 85...275 V AC 50/60 Hz with LXE coil
Drop-out: 0...60 V AC 50/60 Hz with LXE coil
Operational: 85...418 V DC with LXE coil
Drop-out: 0...45 V DC with LXE coil
|
Heat dissipation
|
5.9…7.2 W
2.2…2.5 W
|
Operating time
|
35 ms closing for with LX1/LX9 coil
130 ms opening for with LX1/LX9 coil
30...40 ms closing for with LX4 coil
30...50 ms opening for with LX4 coil
40...80 ms closing for with LXE coil
6...54 ms opening for with LXE coil
|
Mounting support
|
Plate
|
Standards
|
EN 60947-1
JIS C8201-4-1
IEC 60947-1
IEC 60947-4-1
EN 60947-4-1
|
Product certifications
|
ABS
CSA
BV
CB
RINA
RMRoS
DNV
LROS (Lloyds register of shipping)
UL
UKCA
|
Connections - terminals
|
Power circuit: lugs-ring terminals 1 cable(s) 120 mm² - busbar cross section: 25 x 3 mm
Power circuit: connector 1 cable(s) 120 mm²
Power circuit: bar 2 cable(s)
Power circuit: bolted connection
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²
Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²flexible without cable end
Control circuit: screw clamp terminals 1.0 cable(s) 0.25…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²solid without cable end
|
Tightening torque
|
Power circuit: 18 N.m
Control circuit: 1.2 N.m
Control circuit: 0.6 N.m
|
Mechanical durability
|
10 Mcycles
|
Inrush power in VA
|
690…855 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil
543…665 VA (at 20 °C)with LX4 coil
280…310 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil
270…320 VA (at 20 °C)with LXE coil
|
Hold-in power consumption in VA
|
6.6…8.1 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil
3.94…4.83 VA (at 20 °C)with LX4 coil
4.5…7.0 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil
2.5…4.0 VA (at 20 °C)with LXE coil
|
Maximum operating rate
|
2400 cyc/h 55 °C
|
Compatibility code
|
LC1F
|