Range
|
TeSys
|
Product name
|
TeSys F
|
Product or component type
|
Contactor
|
Device short name
|
LC1F
|
Contactor application
|
Motor control
Resistive load
|
Utilisation category
|
AC-4
AC-3
AC-1
|
Poles description
|
3P
|
Power pole contact composition
|
3 NO
|
[Ue] rated operational voltage
|
<= 1000 V AC 50/60 Hz
<= 460 V DC
|
[Ie] rated operational current
|
400 A (at <40 °C) at <= 440 V AC AC-1
330 A (at <55 °C) at <= 440 V AC AC-3
|
Motor power kW
|
160 kW at 1000 V AC 50/60 Hz (AC-3)
160 kW at 380...400 V AC 50/60 Hz (AC-3)
180 kW at 415 V AC 50/60 Hz (AC-3)
200 kW at 440 V AC 50/60 Hz (AC-3)
200 kW at 500 V AC 50/60 Hz (AC-3)
100 kW at 220...240 V AC 50/60 Hz (AC-3)
220 kW at 660...690 V AC 50/60 Hz (AC-3)
59 kW at 400 V AC 50/60 Hz (AC-4)
|
[Uc] control circuit voltage
|
24...1000 V AC 40...400 Hz with LX1/LX9 coil
24...460 V DC with LX4 coil
100...250 V AC 50/60 Hz with LXE coil
100...380 V DC with LXE coil
|
[Uimp] rated impulse withstand voltage
|
8 kV
|
Overvoltage category
|
III
|
[Ith] conventional free air thermal current
|
400 A (at 40 °C)
|
Irms rated making capacity
|
3300 A AC conforming to IEC 60947-4-1
|
Rated breaking capacity
|
2640 A conforming to IEC 60947-4-1
|
[Icw] rated short-time withstand current
|
2650 A 40 °C - 10 s
1800 A 40 °C - 30 s
1300 A 40 °C - 1 min
900 A 40 °C - 3 min
750 A 40 °C - 10 min
|
Associated fuse rating
|
400 A aM at <= 440 V
500 A gG at <= 440 V
|
Average impedance
|
0.28 mOhm - Ith 400 A 50 Hz
|
[Ui] rated insulation voltage
|
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
|
Power dissipation per pole
|
44 W AC-1
31 W AC-3
|
Control circuit voltage limits
|
Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil
Drop-out: 0.35...0.55 Uc AC 40...400 Hz with LX1/LX9 coil
Operational: 0.85...1.1 Uc DC with LX4 coil
Drop-out: 0.15...0.2 Uc DC with LX4 coil
Operational: 85...275 V AC 50/60 Hz with LXE coil
Drop-out: 0...60 V AC 50/60 Hz with LXE coil
Operational: 85...418 V DC with LXE coil
Drop-out: 0...45 V DC with LXE coil
|
Heat dissipation
|
8 W
2.2…5.5 W
|
Operating time
|
40...65 ms closing for with LX1/LX9 coil
100...170 ms opening for with LX1/LX9 coil
40...50 ms closing for with LX4 coil
40...65 ms opening for with LX4 coil
40...80 ms closing for with LXE coil
6...54 ms opening for with LXE coil
|
Mounting support
|
Plate
|
Standards
|
IEC 60947-4-1
JIS C8201-4-1
EN 60947-1
IEC 60947-1
EN 60947-4-1
|
Product certifications
|
ABS
CSA
UL
RMRoS
DNV
CB
BV
LROS (Lloyds register of shipping)
RINA
UKCA
|
Connections - terminals
|
Power circuit: lugs-ring terminals 1 cable(s) 240 mm²
Power circuit: bar 2 cable(s) - busbar cross section: 30 x 5 mm
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²
Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²flexible without cable end
Control circuit: screw clamp terminals 1.0 cable(s) 0.25…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²solid without cable end
|
Tightening torque
|
Power circuit: 35 N.m
Control circuit: 1.2 N.m
Control circuit: 0.6 N.m
|
Mechanical durability
|
10 Mcycles
|
Inrush power in VA
|
600…700 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil
655…803 VA (at 20 °C)with LX4 coil
300…350 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil
300…310 VA (at 20 °C)with LXE coil
|
Hold-in power consumption in VA
|
8…10 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil
3.68…4.53 VA (at 20 °C)with LX4 coil
4.5…7.0 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil
2.5…4.0 VA (at 20 °C)with LXE coil
|
Maximum operating rate
|
2400 cyc/h 55 °C
|
Compatibility code
|
LC1F
|