[Uimp] rated impulse withstand voltage
|
8 kV
|
[Ith] conventional free air thermal current
|
400 A (at 40 °C)
|
Rated breaking capacity
|
2640 A conforming to IEC 60947-4-1
|
[Icw] rated short-time withstand current
|
2650 A 40 °C - 10 s
1800 A 40 °C - 30 s
1300 A 40 °C - 1 min
900 A 40 °C - 3 min
750 A 40 °C - 10 min
|
Associated fuse rating
|
400 A aM at <= 440 V
500 A gG at <= 440 V
|
Average impedance
|
0.28 mOhm - Ith 400 A 50 Hz
|
[Ui] rated insulation voltage
|
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
|
Power dissipation per pole
|
44 W AC-1
31 W AC-3
|
Overvoltage category
|
III
|
Power pole contact composition
|
3 NO
|
Motor power kW
|
160 kW at 380...400 V AC 50/60 Hz (AC-3)
180 kW at 415 V AC 50/60 Hz (AC-3)
200 kW at 440 V AC 50/60 Hz (AC-3)
200 kW at 500 V AC 50/60 Hz (AC-3)
220 kW at 660...690 V AC 50/60 Hz (AC-3)
160 kW at 1000 V AC 50/60 Hz (AC-3)
100 kW at 220...230 V AC 50/60 Hz (AC-3)
59 kW at 400 V AC 50/60 Hz (AC-4)
|
Control circuit voltage limits
|
Operational: 0.85...1.1 Uc (at 55 °C)
Drop-out: 0.15...0.2 Uc (at 55 °C)
|
Mechanical durability
|
10 Mcycles
|
Inrush power in W
|
750 W (at 20 °C)
|
Hold-in power consumption in W
|
5 W at 20 °C
|
Maximum operating rate
|
2400 cyc/h 55 °C
|
Operating time
|
40...50 ms closing
40...65 ms opening
|
Connections - terminals
|
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: lugs-ring terminals 1 cable(s) 240 mm²
Power circuit: bar 2 cable(s) - busbar cross section: 30 x 5 mm
Power circuit: bolted connection
|
Tightening torque
|
Control circuit: 1.2 N.m
Power circuit: 35 N.m
|
Mounting support
|
Plate
|
Heat dissipation
|
5 W
|
Motor power range
|
55…100 kW at 200…240 V 3 phases
110…220 kW at 480…500 V 3 phases
110…220 kW at 380…440 V 3 phases
|
Motor starter type
|
Direct on-line contactor
|
Contactor coil voltage
|
220 V DC standard
|
Standards
|
IEC 60947-4-1
JIS C8201-4-1
EN 60947-4-1
EN 60947-1
IEC 60947-1
|
Product certifications
|
UL
CSA
RINA
DNV
BV
ABS
LROS (Lloyds register of shipping)
RMRoS
CB
UKCA
|
Compatibility code
|
LC1F
|
Control circuit type
|
DC standard
|