[Uc] control circuit voltage
|
48...1000 V AC 40...400 Hz with LX1/LX9 coil
48...440 V DC with LX4 coil
100...250 V AC 50/60 Hz with LXE coil
100...380 V DC with LXE coil
|
[Uimp] rated impulse withstand voltage
|
8 kV
|
Overvoltage category
|
III
|
[Ith] conventional free air thermal current
|
500 A (at 40 °C)
|
Irms rated making capacity
|
4000 A AC conforming to IEC 60947-4-1
|
Rated breaking capacity
|
3200 A conforming to IEC 60947-4-1
|
[Icw] rated short-time withstand current
|
3600 A 40 °C - 10 s
2400 A 40 °C - 30 s
1700 A 40 °C - 1 min
1200 A 40 °C - 3 min
1000 A 40 °C - 10 min
|
Associated fuse rating
|
400 A aM at <= 440 V
500 A gG at <= 440 V
|
Average impedance
|
0.26 mOhm - Ith 500 A 50 Hz
|
[Ui] rated insulation voltage
|
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
|
Power dissipation per pole
|
65 W AC-1
|
Control circuit voltage limits
|
Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil
Drop-out: 0.3...0.5 Uc AC 40...400 Hz with LX1/LX9 coil
Operational: 0.85...1.1 Uc DC with LX4 coil
Drop-out: 0.2...0.35 Uc DC with LX4 coil
Operational: 85...275 V AC 50/60 Hz with LXE coil
Drop-out: 0...60 V AC 50/60 Hz with LXE coil
Operational: 85...418 V DC with LXE coil
Drop-out: 0...45 V DC with LXE coil
|
Heat dissipation
|
14 W
2.2…5.5 W
|
Operating time
|
40...75 ms closing for with LX1/LX9 coil
100...170 ms opening for with LX1/LX9 coil
50...60 ms closing for with LX4 coil
45...60 ms opening for with LX4 coil
40...80 ms closing for with LXE coil
6...54 ms opening for with LXE coil
|
Mounting support
|
Plate
|
Standards
|
JIS C8201-4-1
IEC 60947-4-1
IEC 60947-1
EN 60947-4-1
EN 60947-1
|
Product certifications
|
CB
ABS
DNV
RMRoS
LROS (Lloyds register of shipping)
BV
RINA
UL
CSA
UKCA
|
Connections - terminals
|
Power circuit: bar 2 cable(s) - busbar cross section: 30 x 5 mm
Power circuit: lugs-ring terminals 2 cable(s) 150 mm²
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²
Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²flexible without cable end
Control circuit: screw clamp terminals 1.0 cable(s) 0.25…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²solid without cable end
|
Tightening torque
|
Power circuit: 35 N.m
Control circuit: 1.2 N.m
Control circuit: 0.6 N.m
|
Mechanical durability
|
10 Mcycles
|
Inrush power in VA
|
1000…1150 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil
920…1140 VA (at 20 °C)with LX4 coil
360…470 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil
410…450 VA (at 20 °C)with LXE coil
|
Hold-in power consumption in VA
|
12…18 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil
4…7.5 VA (at 20 °C)with LX4 coil
4.5…7.0 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil
2.5…4.0 VA (at 20 °C)with LXE coil
|
Maximum operating rate
|
2400 cyc/h 55 °C
|
Compatibility code
|
LC1F
|
Packaging without single use plastic
|
No
|
Packaging made with recycled cardboard
|
No
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Compliant with Exemptions
|
Mercury free
|
Yes
|
RoHS exemption information
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
WEEE
|
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
California proposition 65
|
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
|
Take-back
|
No
|
Carbon footprint (kg.eq.CO2 per CR, Total Life cycle)
|
6126
|