Range
|
TeSys
|
Product name
|
TeSys F
|
Product or component type
|
Contactor
|
Device short name
|
LC1F
|
Contactor application
|
Resistive load
Motor control
|
Utilisation category
|
AC-4
AC-3
AC-1
|
Poles description
|
3P
|
Power pole contact composition
|
3 NO
|
[Ue] rated operational voltage
|
<= 1000 V AC 50/60 Hz
<= 460 V DC
|
[Ie] rated operational current
|
780 A (at <55 °C) at <= 440 V AC AC-3
1600 A (at <40 °C) at <= 440 V AC AC-1
|
Motor power kW
|
450 kW at 1000 V AC 50/60 Hz (AC-3)
400 kW at 380...400 V AC 50/60 Hz (AC-3)
425 kW at 415 V AC 50/60 Hz (AC-3)
425 kW at 440 V AC 50/60 Hz (AC-3)
450 kW at 500 V AC 50/60 Hz (AC-3)
220 kW at 220...240 V AC 50/60 Hz (AC-3)
475 kW at 660...690 V AC 50/60 Hz (AC-3)
110 kW at 400 V AC 50/60 Hz (AC-4)
|
[Uc] control circuit voltage
|
110...500 V AC 40...400 Hz with LX1/LX9 coil
48...440 V DC with LX4 coil
|
[Uimp] rated impulse withstand voltage
|
8 kV
|
Overvoltage category
|
III
|
[Ith] conventional free air thermal current
|
1600 A (at 40 °C)
|
Irms rated making capacity
|
7800 A AC conforming to IEC 60947-4-1
|
Rated breaking capacity
|
6240 A conforming to IEC 60947-4-1
|
[Icw] rated short-time withstand current
|
3000 A 40 °C - 3 min
6250 A 40 °C - 10 s
5600 A 40 °C - 30 s
4600 A 40 °C - 1 min
2200 A 40 °C - 10 min
|
Associated fuse rating
|
800 A aM at <= 440 V
1600 A gG at <= 440 V
|
Average impedance
|
0.1 mOhm - Ith 1600 A 50 Hz
|
[Ui] rated insulation voltage
|
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
|
Power dissipation per pole
|
60 W AC-3
250 W AC-1
|
Control circuit voltage limits
|
Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil
Drop-out: 0.2...0.4 Uc AC 40...400 Hz with LX1/LX9 coil
Operational: 0.85...1.1 Uc DC with LX4 coil
Drop-out: 0.2...0.4 Uc DC with LX4 coil
|
Heat dissipation
|
22 W
|
Operating time
|
40...80 ms closing for with LX1/LX9 coil
130...230 ms opening for with LX1/LX9 coil
70...80 ms closing for with LX4 coil
100...130 ms opening for with LX4 coil
|
Mounting support
|
Plate
|
Standards
|
IEC 60947-1
IEC 60947-4-1
EN 60947-1
JIS C8201-4-1
EN 60947-4-1
|
Product certifications
|
UL
LROS (Lloyds register of shipping)
RINA
DNV
CCC
BV
CB
ABS
UKCA
|
Connections - terminals
|
Power circuit: bar 2 cable(s) - busbar cross section: 100 x 5 mm
Power circuit: bolted connection
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²
|
Tightening torque
|
Power circuit: 58 N.m
Control circuit: 1.2 N.m
|
Mechanical durability
|
5 Mcycles
|
Inrush power in VA
|
1900…2300 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil
1960…2420 VA (at 20 °C)with LX4 coil
|
Hold-in power consumption in VA
|
44…55 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil
42…52 VA (at 20 °C)with LX4 coil
|
Maximum operating rate
|
600 cyc/h 55 °C
|
Compatibility code
|
LC1F
|