Control circuit type
|
AC at 50/60 Hz
|
[Uc] control circuit voltage
|
240 V AC 50/60 Hz
|
[Ith] conventional free air thermal current
|
12 A (at 55 °C) for power circuit
|
Irms rated making capacity
|
66 A at 690 V AC conforming to IEC 60947
66 A at 690 V AC conforming to NF C 63-110
|
Rated breaking capacity
|
52 A at <= 400 V for power circuit conforming to NF C 63-110
52 A at <= 400 V for power circuit conforming to IEC 60947
|
[Icw] rated short-time withstand current
|
50 A 55 °C for power circuit
|
Associated fuse rating
|
16 A gI at <= 440 V for power circuit conforming to IEC 60947
|
Average impedance
|
4 mOhm - Ith 12 A 50 Hz
|
[Ui] rated insulation voltage
|
690 V conforming to IEC 60947
690 V conforming to VDE 0110 group C
690 V conforming to BS 5424
690 V conforming to UL 508
690 V conforming to CSA C22.2 No 14
|
Mounting support
|
Rail
|
Standards
|
EN/IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
|
Product certifications
|
CB Scheme
CE
UKCA
EAC
cULus
|
Connections - terminals
|
Power circuit: connector 1 cable(s) 0.35…6 mm²flexible with cable end
Power circuit: connector 1 cable(s) 0.5…6 mm²flexible without cable end
Power circuit: connector 1 cable(s) 1.5…6 mm²solid
Power circuit: connector 2 cable(s) 0.35…1.5 mm²flexible with cable end
Power circuit: connector 2 cable(s) 0.35…2.5 mm²flexible without cable end
Power circuit: connector 2 cable(s) 1.5…4 mm²solid
|
Tightening torque
|
0.8 N.m - on connector - with screwdriver pozidriv No 1
|
Operating time
|
6...8 ms coil de-energisation and NO opening
7...14 ms coil energisation and NO closing
|
Mechanical durability
|
10 Mcycles
|
Maximum operating rate
|
1200 cyc/h
|
Control circuit voltage limits
|
Operational: 0.85...1.1 Uc (at <50 °C)
Drop-out: 0.2...0.75 Uc (at <50 °C)
|
Inrush power in VA
|
16 VA (at 20 °C)
|
Hold-in power consumption in VA
|
4.2 VA (at 20 °C)
|
Heat dissipation
|
1.4 W at 50/60 Hz
|