Range
|
TeSys
|
Product name
|
TeSys F
|
Product or component type
|
Reversing contactor
|
Device short name
|
LC2F
|
Contactor application
|
Motor control
Resistive load
|
Utilisation category
|
AC-3
AC-1
|
Device presentation
|
Preassembled with reversing power busbar
|
Poles description
|
3P
|
Power pole contact composition
|
3 NO
|
[Ue] rated operational voltage
|
<= 1000 V AC 50/60 Hz
<= 460 V DC
|
[Ie] rated operational current
|
350 A (at <40 °C) at <= 440 V AC AC-1
265 A (at <55 °C) at <= 440 V AC AC-3
|
Motor power kW
|
132 kW at 380...400 V AC 50/60 Hz
140 kW at 415 V AC 50/60 Hz
140 kW at 440 V AC 50/60 Hz
147 kW at 1000 V AC 50/60 Hz
160 kW at 500 V AC 50/60 Hz
75 kW at 220...240 V AC 50/60 Hz
160 kW at 660...690 V AC 50/60 Hz
|
Auxiliary contact composition
|
1 NO
|
[Uimp] rated impulse withstand voltage
|
8 kV
|
Overvoltage category
|
III
|
[Ith] conventional free air thermal current
|
350 A (at 40 °C)
|
Irms rated making capacity
|
2650 A AC conforming to IEC 60947-4-1
|
Rated breaking capacity
|
2120 A conforming to IEC 60947-4-1
|
[Icw] rated short-time withstand current
|
2200 A 40 °C - 10 s
1230 A 40 °C - 30 s
950 A 40 °C - 1 min
620 A 40 °C - 3 min
480 A 40 °C - 10 min
|
Associated fuse rating
|
315 A aM at <= 440 V
400 A gG at <= 440 V
|
Average impedance
|
0.3 mOhm - Ith 350 A 50 Hz
|
[Ui] rated insulation voltage
|
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
|
Power dissipation per pole
|
21 W AC-3
|
Interlocking type
|
Mechanical
|
Mounting support
|
Plate
|
Standards
|
JIS C8201-4-1
IEC 60947-4-1
EN 60947-4-1
EN 60947-1
IEC 60947-1
|
Product certifications
|
RMRoS
UL
LROS (Lloyds register of shipping)
DNV
CCC
RINA
CSA
ABS
CB
UKCA
|
Connections - terminals
|
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: connector 1 cable(s) 240 mm²
Power circuit: lugs-ring terminals 1 cable(s) 240 mm²
Power circuit: bar 2 cable(s) - busbar cross section: 32 x 4 mm
|
Tightening torque
|
Control circuit: 1.2 N.m
Power circuit: 35 N.m
|