LE1D12P7A04
Enclosed DOL starter,TeSys LE,12A,230V AC coil,including 1 LC1D
|
|
|
Main
Range
|
TeSys
|
Product name
|
TeSys LE
|
Device short name
|
LE1D
|
Product or component type
|
Enclosed DOL starter
|
Device application
|
Standard
|
Utilisation category
|
AC-3
|
Device composition
|
Thermal overload relay ordered separately
Contactor
|
Control type
|
Without
|
Complementary
Motor power kW
|
3 kW at 220/230 V AC 50/60 Hz
7.5 kW at 500 V AC 50/60 Hz
7.5 kW at 660/690 V AC 50/60 Hz
5.5 kW at 380/400 V AC 50/60 Hz
5.5 kW at 415 V AC 50/60 Hz
5.5 kW at 440 V AC 50/60 Hz
|
[Ith] Conventional free air thermal current
|
12 A
|
[Uc] control circuit voltage
|
230 V AC 50/60 Hz
|
Cable entry number
|
2 ISO20 top
2 ISO20 bottom
|
Width
|
88 mm
|
Height
|
166 mm
|
Depth
|
120 mm
|
Net weight
|
0.92 kg
|
Environment
Material
|
Polycarbonate
|
IP degree of protection
|
IP65 conforming to IEC 60529
|
IK degree of protection
|
IK07 conforming to IEC 60529
|
Standards
|
IEC 60947-4-1
|
Ambient air temperature for operation
|
-5…40 °C
|
Environmental characteristic
|
Standard environment
|
Product certifications
|
UKCA
|
Packing Units
Unit Type of Package 1
|
PCE
|
Number of Units in Package 1
|
1
|
Package 1 Height
|
15.5 cm
|
Package 1 Width
|
15.0 cm
|
Package 1 Length
|
20.5 cm
|
Package 1 Weight
|
920.0 g
|
Offer Sustainability
Packaging without single use plastic
|
Yes
|
Packaging made with recycled cardboard
|
Yes
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Compliant
EU RoHS Declaration
|
Toxic heavy metal free
|
Yes
|
Mercury free
|
Yes
|
RoHS exemption information
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
WEEE
|
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
Carbon footprint (kg.eq.CO2 per CR, Total Life cycle)
|
107
|