LG1K065M706
Enclosed DOL starter,TeSys LG,1-1.6A,220/230V AC coil,including 1 LC1K,GV2ME,rotary isolation switch ,2 pushbuttons
|
|
|
Main
Range
|
TeSys
|
Product name
|
TeSys LG
|
Device short name
|
LG1K
|
Product or component type
|
Enclosed DOL starter
|
Device application
|
Safety
|
Utilisation category
|
AC-3
|
Device composition
|
Contactor
Switch disconnector
Circuit-breaker
|
Motor power kW
|
0.25 kW at 220/230 V AC 50/60 Hz
0.55 kW at 400/415 V AC 50/60 Hz
0.55 kW at 440 V AC 50/60 Hz
|
Thermal protection adjustment range
|
1…1.6 A
|
[Uc] control circuit voltage
|
220/230 V AC 50/60 Hz
|
Control type
|
Push-button start white I
Push-button stop black O
Rotary handle emergency stop red
|
Complementary
Cable entry number
|
4 2 Pg 13 + 2 Pg 16 top
4 2 Pg 13 + 2 Pg 16 bottom
|
Width
|
175 mm
|
Height
|
165 mm
|
Depth
|
165 mm
|
Net weight
|
0.97 kg
|
Environment
Standards
|
IEC 60947-4-1
IEC 60204-1
|
Product certifications
|
CE
UKCA
|
Material
|
Polycarbonate
|
IK degree of protection
|
IK07 conforming to IEC 60529
|
IP degree of protection
|
IP55 conforming to IEC 60529
|
Environmental characteristic
|
Standard environment
|
Packing Units
Unit Type of Package 1
|
PCE
|
Number of Units in Package 1
|
1
|
Package 1 Height
|
18.0 cm
|
Package 1 Width
|
22.5 cm
|
Package 1 Length
|
25.5 cm
|
Package 1 Weight
|
1.75 kg
|
Unit Type of Package 2
|
P06
|
Number of Units in Package 2
|
12
|
Package 2 Height
|
77.0 cm
|
Package 2 Width
|
80.0 cm
|
Package 2 Length
|
60.0 cm
|
Package 2 Weight
|
29.5 kg
|
Offer Sustainability
Contractual warranty
|
|