Network frequency
|
50...60 Hz
|
Mounting support
|
Direct on contactor
Rail
|
Tripping threshold
|
1.2...6 A
|
Surge withstand
|
6 kV conforming to IEC 61000-4-5
|
Contacts type and composition
|
1 C/O
|
[Ith] conventional free air thermal current
|
3 A for control circuit
|
Protection type
|
BS fuse 3 A - for control circuit
GB2 circuit breaker 3 A - for control circuit
GG fuse 3 A - for control circuit
|
Maximum power
|
28 W at 110 V DC conforming to IEC 60947
28 W at 220 V DC conforming to IEC 60947
55 W at 24 V DC conforming to IEC 60947
55 W at 48 V DC conforming to IEC 60947
140 VA at 48 V AC conforming to IEC 60947
360 VA at 110 V AC conforming to IEC 60947
360 VA at 220 V AC conforming to IEC 60947
70 VA at 24 V AC conforming to IEC 60947
|
[Ui] rated insulation voltage
|
Power circuit: 600 V conforming to CSA
Power circuit: 600 V conforming to UL
Power circuit: 690 V conforming to IEC 60947-4-1
|
[Uimp] rated impulse withstand voltage
|
6 kV
|
Phase failure sensitivity
|
< 3 s
|
Reset
|
Automatic reset 120 s fixed
Electrical by interruption of power supply for minimum 0.1 s
Manual reset
|
Time range
|
0.2...10 s - O-time knob
0.3...10 s - O-time knob
0.5..30 s - D-time knob
|
Signalling function
|
2 LEDs
|
Connections - terminals
|
Control circuit: cable 1 x 1…25 mm²flexible with cable end
Control circuit: cable 1 x 1…25 mm²flexible without cable end
Power circuit: cable 1 x 1…4 mm²flexible with cable end
Power circuit: cable 1 x 1.5…10 mm²flexible without cable end
Power circuit: lug-clamp 1 x 1…4 mm²flexible with cable end
Power circuit: lug-clamp 1 x 1.5…10 mm²flexible without cable end
Control circuit: cable 2 x 1…25 mm²flexible with cable end
Control circuit: cable 2 x 1…25 mm²flexible without cable end
Control circuit: lug-clamp 1 x 1…25 mm²flexible with cable end
Control circuit: lug-clamp 1 x 1…25 mm²flexible without cable end
Control circuit: lug-clamp 2 x 1…25 mm²flexible with cable end
Control circuit: lug-clamp 2 x 1…25 mm²flexible without cable end
|
Tightening torque
|
Control circuit: 0.6...1.2 N.m on lug-clamp
Power circuit: 2 N.m on cable
|
Height
|
67.5 mm
|
Width
|
45 mm
|
Depth
|
67.5 mm
|
Net weight
|
0.172 kg
|
Standards
|
IEC 60947
IEC 60255-6
|
Product certifications
|
GOST
CSA
UL
|
Protective treatment
|
TH conforming to IEC 60068
|
IP degree of protection
|
IP20 conforming to IEC 60529
|
Ambient air temperature for operation
|
-25…60 °C conforming to IEC 60947-4-1
|
Ambient air temperature for storage
|
-30…80 °C
|
Operating altitude
|
2000 m
|
Fire resistance
|
850 °C conforming to IEC 60695-2-1
|
Shock resistance
|
15 gn 11 ms conforming to IEC 60068-2-7
|
Vibration resistance
|
4 gn conforming to IEC 60068-2-6
|
Dielectric strength
|
2 V 50 Hz conforming to IEC 60255-5
|
Resistance to electrostatic discharge
|
6 kV in indirect mode
8 kV in air
|
Resistance to radiated fields
|
10 V/m level 3
|
Resistance to fast transients
|
2 kV
|
Disturbance radiated/conducted
|
10 V conforming to EN 61000-4-6
Class A conforming to EN 55011
|