Network frequency
|
50...60 Hz
|
[Us] rated supply voltage
|
24 V DC
|
Supply voltage limits
|
17…32 V
|
Mounting support
|
Under contactor
Rail
|
Tripping threshold
|
1.05 +/- 0.06 In alarm conforming to IEC 60947-4-1
1.12 +/- 0.06 In de-energisation conforming to IEC 60947-4-1
|
Auxiliary contact composition
|
1 NO + 1 NC
|
[Ith] conventional free air thermal current
|
5 A for signalling circuit
|
[Ue] rated operational voltage
|
690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
|
Associated fuse rating
|
4 A gG for signalling circuit
4 A BS for signalling circuit
|
[Uimp] rated impulse withstand voltage
|
6 kV conforming to IEC 60947-1
|
Phase failure sensitivity
|
Tripping in 4 s +/- 20 % conforming to IEC 60947-4-1
|
Control type
|
Red push-button: stop
Blue push-button: reset
|
Temperature compensation
|
-20…60 °C
|
Switching capacity in mA
|
0...150 mA
|
Maximum voltage drop
|
<2.5 V closed state
|
Connections - terminals
|
Power circuit: bars
Control circuit: screw clamp terminals 1 cable(s) 0.5…1.5 mm² flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 0.5…1.5 mm² flexible without cable end
Alarm circuit: screw clamp terminals 1 cable(s) 0.5…1.5 mm² flexible without cable end
|
Tightening torque
|
Alarm circuit: 0.45 N.m - on screw clamp terminals
Power circuit: 18 N.m - on bars M8
Control circuit: 1.2 N.m - on screw clamp terminals
|
Height
|
118 mm
|
Width
|
115 mm
|
Depth
|
125 mm
|
Product weight
|
0.9 kg
|
Climatic withstand
|
Conforming to IACS E10
|
IP degree of protection
|
IP20 conforming to IEC 60529
|
Ambient air temperature for operation
|
-20…60 °C without derating conforming to IEC 60947-4-1
|
Ambient air temperature for storage
|
-60…70 °C
|
Operating altitude
|
<= 2000 m without derating
|
Mechanical robustness
|
Vibrations: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Shocks: 13 Gn for 11 ms conforming to IEC 60068-2-7
|
Dielectric strength
|
1.89 kV at 50 Hz conforming to IEC 60947-1
|
Standards
|
EN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/T 14048.4
GB/T 14048.5
|
Product certifications
|
UL
CSA
CCC
UKCA
|
SCIP Number
|
D5a17874-1166-4927-b008-33d15e304a41
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Compliant with Exemptions
|
Mercury free
|
Yes
|
RoHS exemption information
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
WEEE
|
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
PVC free
|
Yes
|
California proposition 65
|
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
|
Take-back
|
No
|
Carbon footprint (kg CO2 eq, Total Life cycle)
|
133
|