Schneider-Electric
 
LV432695 picture- web-product-data-sheet
LV432695
circuit breaker Compact NSX400H, 70 kA at 415 VAC, Micrologic 2.3 trip unit 400 A, 3 poles 3d
Schneider Electric
Characteristics
Main
Range Compact
Product name Compact NSX
Product or component type Circuit breaker
Device short name Compact NSX400H
Device application Distribution
Poles description 3P
Protected poles description 3t
Network type AC
Network frequency 50/60 Hz
[In] rated current 400 A at 40 °C
[Ui] rated insulation voltage 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 kV
[Ue] rated operational voltage 690 V AC 50/60 Hz
Breaking capacity code H 70 kA 415 V AC
Breaking capacity 85 kA at 240 V AC 50/60 Hz conforming to UL 508
65 kA at 480 V AC 50/60 Hz conforming to UL 508
100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA at 600 V AC 50/60 Hz conforming to UL 508
20 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
Suitability for isolation Yes conforming to EN 60947-2
Yes conforming to IEC 60947-2
Utilisation category Category A
Trip unit name Micrologic 2.3
Trip unit technology Electronic
Trip unit protection functions LSoI
Pollution degree 3 conforming to IEC 60664-1
Complementary
Control type Toggle
Mounting mode Fixed
Mounting support Backplate
Upside connection Front
Downside connection Front
Auxiliary contact composition Without
Mechanical durability 15000 cycles
Electrical durability 12000 cycles 440 V In/2 conforming to IEC 60947-2
3000 cycles 690 V In conforming to IEC 60947-2
6000 cycles 440 V In conforming to IEC 60947-2
6000 cycles 690 V In/2 conforming to IEC 60947-2
Connection pitch 45 mm
Local signalling LED 105 % Ir
LED 90 % Ir
LED ready
Protection type L : for overload protection (long time)
So : for short time short-circuit protection with fixed delay
I : for instantaneous short-circuit protection
Trip unit rating 400 A at 40 °C
Long time pick-up adjustment type Ir Adjustable 9 settings
Long time pick-up adjustment range 0.9...1 x Io
Long time delay adjustment type Fixed
[tr] long-time delay adjustment range 16 s at 6 x Ir
Thermal memory 20 minutes before and after tripping
Short-time pick-up adjustment type Isd Adjustable 9 settings
[Isd] short-time pick-up adjustment range 1.5...10 x Ir
Short-time delay adjustment type Fixed
Instantaneous pick-up adjustment type Ii Fixed
Instantaneous pick-up adjustment range 4800 A
Height 255 mm
Width 140 mm
Depth 110 mm
Net weight 6.05 kg
Compatibility code NSX400
Environment
Overvoltage category Class II
Electrical shock protection class Class II
Standards EN/IEC 60947
UL 508
Product certifications CCC
Marine
EAC
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to IEC 62262
Ambient air temperature for operation -35…70 °C
Ambient air temperature for storage -55…85 °C
Offer Sustainability
Sustainable offer status Green Premium product
EU RoHS Directive Compliant
print EU RoHS Declaration
Mercury free Yes
RoHS exemption information
print Yes
China RoHS Regulation
print China RoHS declaration
Environmental Disclosure
print Product Environmental Profile
Circularity Profile
print End of Life Information
WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Contractual warranty
Warranty 18 months