LV434021
energy sensor PowerTag Monoconnect 250A 3P+N
|
|
|
Main
Range of product
|
PowerLogic
|
Product name
|
PowerTag M250
|
Product or component type
|
Energy sensor
|
Poles
|
3P + N
|
Maximum current [Imax]
|
250 A
|
[Ib] Basic current
|
40 A
|
Starting current
|
160 mA
|
Saturation current
|
500 A
|
Product specific application
|
Energy management
Overload alarm
Power factor
Load monitoring
Circuit monitoring
|
Concentrator compatibility
|
Acti9 Smartlink SI B
Acti9 Smartlink SI D
Acti9 PowerTag Link C
Acti9 PowerTag Link
Acti9 PowerTag Link HD
Harmony Hub
Wiser IP module
EcoStruxure Panel Server Universal
EcoStruxure Panel Server Advanced
PrismaSet Active
|
Range compatibility
|
Compact NSX Compact NSX100...250
Compact INV Compact INV100...250
Compact NS Compact NS100...250
Compact INS Compact INS250-100...250
EasyPact EasyPact CVS100
EasyPact EasyPact CVS160
EasyPact EasyPact CVS250
|
Type of measurement
|
Active and reactive energy
Active and reactive power
Apparent power
Current
Voltage
Power factor
|
Accuracy class
|
Class 1 active energy conforming to IEC 61557-12
Class 2 reactive energy conforming to IEC 61557-12
Class 1 active power conforming to IEC 61557-12
Class 2 reactive power conforming to IEC 61557-12
Class 2 apparent power conforming to IEC 61557-12
Class 1 current conforming to IEC 61557-12
Class 0.5 voltage conforming to IEC 61557-12
Class 1 power factor conforming to IEC 61557-12
|
Metering type
|
Power factor 0...1: class 1 at 25 °C conforming to IEC 61557-12
Active energy Ep IN/OUT/tot 0...281 x 10exp(9) kWh: class 1 at 25 °C conforming to IEC 61557-12
Reactive energy Ep IN/OUT/tot 0...281 x 10exp(9) kVARh: class 2 at 25 °C conforming to IEC 61557-12
Voltage U12, U23, U31 320...480 V: class 0.5 at 25 °C conforming to IEC 61557-12
Voltage V1N, V2N, V3N 184...276 V: class 0.5 at 25 °C conforming to IEC 61557-12
Current I1, I2, I3, Iavg 8...250 A: class 1 at 25 °C conforming to IEC 61557-12
Apparent power S, S1, S2, S4 88 VA...416 kVA: class 2 at 25 °C conforming to IEC 61557-12
Active power P, P1, P2, P4 88 W...416 kW: class 1 at 25 °C conforming to IEC 61557-12
Reactive power Q, Q1, Q2, Q4 88 VAR...416 kVAR: class 2 at 25 °C conforming to IEC 61557-12
Frequency 45...65 Hz
|
Mounting location
|
Bottom
|
Mounting support
|
On circuit breaker
|
Connection pitch
|
35 mm
|
Product destination
|
Switchboard
|
Event management
|
Voltage loss with measured current at voltage loss
|
Transmission support medium
|
Radio frequency 2.4…2.4835 GHz conforming to IEEE 802.15.4 (11…26) transmission time < 5 ms
|
Maximum emission power
|
10 mW
|
Complementary
[Imp] maximum permanent current
|
1.2 x In
|
Mounting mode
|
Bolt-on
|
Tightening torque
|
10 N.m
|
Supply voltage
|
230 V AC, +/- 20 %, between phase and neutral
400 V AC, +/- 20 %, between phases
|
Network frequency
|
50 Hz
60 Hz
|
Maximum power consumption
|
3.7 VA
|
Standards
|
IEC 61557-12
IEC 61010-1
ETSI EN 301 487-1
IEC 61010-2-030
IEC 61326-1
ETSI EN 300 328
|
Height
|
57 mm
|
Width
|
140 mm
|
Depth
|
86 mm
|
Net weight
|
300 g
|
Colour
|
Dark grey (RAL 7016)
|
Environment
Quality labels
|
CE
|
Directives
|
2014/53/EU - radio equipment directive
|
Operating altitude
|
0...2000 m
|
Ambient air temperature for operation
|
-25…70 °C
|
Ambient air temperature for storage
|
-50…85 °C
|
Overvoltage category
|
IV conforming to IEC 61010-1
|
Measurement category
|
Category III conforming to IEC 61010-2-030
|
IP degree of protection
|
IP20
|
IK degree of protection
|
IK07 conforming to IEC 60068-2-75 test Ehb
|
Pollution degree
|
3
|
Relative humidity
|
0…95 % at 55 °C conforming to IEC 60721-3-3
|
Vibration resistance
|
3M4 conforming to IEC 60721-3-3
|
Electromagnetic compatibility
|
Industrial electromagnetic environment conforming to IEC 61326-1
Radiated EMC conforming to ETSI EN 301 489-17
Electromagnetic emission conforming to IEC 62311
|
Environmental characteristics
|
Indoor use
|
Packing Units
Unit Type of Package 1
|
PCE
|
Number of Units in Package 1
|
1
|
Package 1 Height
|
13.0 cm
|
Package 1 Width
|
11.0 cm
|
Package 1 Length
|
17.3 cm
|
Package 1 Weight
|
536.0 g
|
Unit Type of Package 2
|
S02
|
Number of Units in Package 2
|
4
|
Package 2 Height
|
15.0 cm
|
Package 2 Width
|
30.0 cm
|
Package 2 Length
|
40.0 cm
|
Package 2 Weight
|
2.5 kg
|
Unit Type of Package 3
|
P06
|
Number of Units in Package 3
|
64
|
Package 3 Height
|
71.5 cm
|
Package 3 Width
|
80.0 cm
|
Package 3 Length
|
60.0 cm
|
Package 3 Weight
|
47.0 kg
|
Offer Sustainability
SCIP Number
|
Defcd2b6-ad55-40e6-9ed1-e4eaa37e615b
|
BVB
|
Accepted
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Compliant with Exemptions
|
Mercury free
|
Yes
|
RoHS exemption information
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
California proposition 65
|
"WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov"
|
Contractual warranty
|
|