Trip unit name
|
MicroLogic
|
Power supply type
|
Regulated switch mode
|
[Us] rated supply voltage
|
200...240 V AC 50/60 Hz tolerance: +10 % -15 %
|
Input voltage limits
|
170...264 V AC at 47.5…63 Hz
|
Output voltage
|
24 V DC +/-5 %
|
Overvoltage category
|
IV conforming to IEC 62477-1
III conforming to UL 61010-1
|
Power supply output current
|
1 A
|
Rated power in W
|
24 W
|
Output protection type
|
Against overload, protection technology: manual reset
Against overvoltage, protection technology: 30...32 V, manual reset
Against short-circuits, protection technology: manual reset
Thermal, protection technology: automatic reset
|
Inrush current
|
20 A 2 ms
|
Efficiency
|
85 %
|
Power dissipation in W
|
4.2 W
|
Holding time
|
>= 20 ms 200...240 V AC
|
Permissible temporary current boost
|
1.5 A (200 ms)
|
Connections - terminals
|
Screw type terminals, connection capacity: 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16
Screw type terminals, connection capacity: 1 x 0.2...1 x 4 mm² AWG 24...AWG 12
|
Mounting support
|
35 x 7.5 mm symmetrical DIN rail
|
Operating position
|
Horizontal
|
Operating altitude
|
0...2000 m
|
Name of test
|
Electrostatic discharges conforming to EN/IEC 61000-4-2
Induced electromagnetic field conforming to EN/IEC 61000-4-6
Magnetic field conforming to EN 61000-4-8
Primary outage conforming to IEC 61000-4-11
Radiated electromagnetic field conforming to EN/IEC 61000-4-3
Rapid transient conforming to IEC 61000-4-4
Surge conforming to EN/IEC 61000-4-5
Radiated emissions conforming to EN 61000-6-3
Conducted emissions on the power line conforming to EN 61000-6-3
|
Status LED
|
1 LED (green) output voltage
|
Height
|
90 mm
|
Width
|
108 mm
|
Depth
|
67.5 mm
|