Power quality analysis
|
EN 50160 compliance checking
Conforming to IEEE 519 harmonic limit
Conforming to IEC 61000-4-30: class A compliance reporting
Conforming to IEEE 519 compliance reporting
Waveform capture
Total demand distortion
Total harmonic distortion
Up to the 63rd harmonic
Up to the 127th harmonic with software
Disturbance direction detection
Dip, swell and transient
Half cycle data acquisition
Transient detection (20 µs)
|
Type of measurement
|
Voltage sags and swells
Current sags and swells
Voltage
Current
Frequency
Active and reactive power total
Apparent power total
Active and reactive power per phase
Apparent power per phase
Power factor total
Power factor per phase
Active and reactive energy
Apparent energy
Harmonic distorsion (I THD & U THD)
|
[Us] rated supply voltage
|
90...480 V AC 45...66 Hz +/- 10 %
90...120 V AC 400 Hz +/- 10 %
110...480 V DC +/- 10 %
|
Network frequency
|
50 Hz
60 Hz
|
Ride-through time
|
100 ms 6 cycles at 60 Hz 120 V AC typical
400 ms 24 cycles at 60 Hz 240 V AC typical
1200 ms 72 cycles at 60 Hz 480 V AC typical
|
[In] rated current
|
1 A
5 A
|
Type of network
|
3P + N + E
|
Power consumption in VA
|
38 VA at 480 V AC
|
Maximum power consumption in VA
|
80 VA at 480 V AC
|
Display type
|
Without display
|
Sampling rate
|
1024 samples/cycle
|
Measurement current
|
0.01…20 A
|
Input type
|
Voltage (impedance 5 MOhm)
External CT (impedance 0.3 mOhm)5 x
|
Measurement voltage
|
57…400 V AC 42...69 Hz between phase and neutral
100…690 V AC 42...69 Hz between phases
|
Frequency measurement range
|
20…450 Hz
|
Number of inputs
|
8 digital 30 V AC/60 V DC
|
Measurement accuracy
|
Voltage +/- 0.1 %
Current +/- 0.1 %
|
Accuracy class
|
Class 0.1S active energy conforming to IEC 62053-22
Class 0.1 active energy conforming to IEC 61557-12
Class 0.1 active energy conforming to ANSI C12.20
Class 0.5S reactive energy conforming to IEC 62053-24
Class 0.1 current conforming to IEC 61557-12
Class 0.1 voltage conforming to IEC 61557-12
Class 0.1 active power conforming to IEC 61557-12
Class 0.5 power factor conforming to IEC 61557-12
|
Number of outputs
|
4 digital
2 form C relay
|
Communication port protocol
|
Modbus RTU at 2400...115200 bps - 2-wire
ION at 2400...115200 bps - 2-wire
DNP3 at 2400...115200 bps - 2-wire
Modbus TCP at 10/100 Mbit/s
ION TCP at 10/100 Mbit/s
DNP3 TCP at 10/100 Mbit/s
IEC 61850
Ethernet Modbus TCP/IP daisy chain at 10/100 Mbit/s
DHCP
DNS
DLMS
|
Communication port support
|
RS485 2 removable screw terminal block
|
Port Ethernet
|
10/100BASE-TX 2 RJ45
|
Communication gateway
|
Ethernet/serial
|
Time synchronisation protocol
|
GPS
IRIG-B
NTP
SNTP
PTP
|
Data recording
|
Time stamping
Min/max of instantaneous values
User-definable data logs
Continuous logging or snapshot
Trending/forecasting
Event logs
Alarm logs
Configuration change
Power outage
User login/logout
Data logs
GPS synchronisation
Sequence of event recording
|
Memory capacity
|
2 GB
|
Cybersecurity
|
Syslog protocol support
Robust security logs
Port hardening
Enable/disable communication ports
Hardware metrology lock
|
Web services
|
Viewing of captured waveform
Web page
Pass/fail report for IEEE 519
Pass/fail report for EN 50160
ITIC (CBEMA) curve
SEMI curve
NEMA motor derating curve
Alarm notification by e-mail
TLS 1.2
Push historical data via mail
|
Ethernet service
|
DHCP client
Device Profile Web Services (DPWS)
Rapid Scanning Tree Protocol (RSTP)
FTP/HTTP/HTTPS
|
Communication service
|
Compliant reports
Power quality summary
Energy report
EcoStruxure Power Events Analysis
SMTP e-mail notification
SNMP
|
Tamperproof of settings
|
Protected by sealable cover
|
Mounting support
|
DIN rail
|
Electrical insulation class
|
Class III conforming to EN/IEC 62052-11
|
Isolation voltage
|
III400…690 V conforming to EN 61010-1:ed. 3
III347…600 V conforming to UL 61010-1:ed. 3
III347…600 V conforming to CSA C22.2 No 61010-1:ed. 3
|
Width
|
160 mm
|
Depth
|
135.3 mm
|
Height
|
160 mm
|
Product weight
|
1.5 kg
|