Power quality analysis
|
Up to the 15th harmonic
|
Device application
|
Multi-tariff
Power monitoring
Sub billing
|
Type of measurement
|
Active and reactive power
Apparent power
Current
Voltage
Energy
Power factor
Frequency
Total current harmonic distortion THD (I)
Total voltage harmonic distortion THD (U)
|
Supply voltage
|
100...277 V AC 45...65 Hz
173...480 V AC 45...65 Hz
100...300 V DC
|
Network frequency
|
60 Hz
50 Hz
|
[In] rated current
|
5 A
1 A
|
Type of network
|
3P
3P + N
1P + N
|
Power consumption in VA
|
5 VA
|
Display type
|
Backlit LCD
|
Display resolution
|
128 x 96 pixels
|
Sampling rate
|
32 samples/cycle
|
Measurement current
|
0.02…1.2 A
0.05…6 A
|
Analogue input type
|
Current 0...5 A
Current 0...1 A
|
Measurement voltage
|
50…330 V AC 45...65 Hz direct
50…330 V AC 45...65 Hz phase to neutral
80…570 V AC 45...65 Hz direct
80…570 V AC 45...65 Hz phase to phase
570…999000 V AC 45...65 Hz with external VT
|
Frequency measurement range
|
45…65 Hz
|
Number of inputs
|
2 digital 0...4 mA 11...40 V DC
|
Measurement accuracy
|
Current 0.3 % 0.5...6 A
Current 0.5 % 0.1...1.2 A
Voltage 0.3 % 50...330 V
Voltage 0.3 % 80...570 V
|
Accuracy class
|
Class 0.5S active energy conforming to IEC 62053-22
Class 1 active energy conforming to IEC 62053-21
Class 2 reactive energy conforming to IEC 62053-23
Class C active energy conforming to EN 50470-3
|
Number of outputs
|
2 digital (static)
|
Information displayed
|
Tariff (4)
|
Communication port protocol
|
Modbus at 9.6...38.4 kbauds
|
Communication port support
|
RS485
|
Data recording
|
Energy consumption logs
15 alarms
Power logs
Time stamping
Min/max of instantaneous values
|
Memory capacity
|
512 KB
|
Mounting mode
|
Clip-on
|
Mounting support
|
DIN rail
|
Standards
|
BS EN 61557-12
IEC 61557-12
EN 61557-12
BS EN 61326-1
IEC 61326-1
EN 61326-1
BS EN 62052-11
IEC 62052-11
EN 62052-11
BS EN 62053-21
IEC 62053-21
EN 62053-21
BS EN 62053-22
IEC 62053-22
EN 62052-22
BS EN 62053-23
IEC 62053-23
EN 62052-23
BS EN 61010-1
EN 61010-1
IEC 61010-1
UL 61010-1
BS EN 61010-2-30
IEC 61010-2-30
EN 61010-2-30
UL 61010-2-30
ANSI C12.20
|
Product certifications
|
CE conforming to IEC 61010-1 (safety)
CE conforming to EN 61557-12 (power monitor)
CE conforming to EN/IEC 61326-1 (EMC)
UKCA conforming to BS EN 61010-1 (safety)
UKCA conforming to BS EN 61557-12 (power monitor)
UKCA conforming to BS EN 61326-1 (EMC)
CULus conforming to EN 61010-1 (safety)
CULus conforming to UL 61010-1 (safety)
EAC (sub-meter)
RCM
|
Width
|
90 mm
|
Depth
|
70 mm
|
Height
|
95 mm
|
Product weight
|
0.26 kg
|