Power quality analysis
|
Up to the 31st harmonic
|
Device application
|
Multi-tariff
Power monitoring
|
Type of measurement
|
Current
Voltage
Frequency
Power factor
Energy
Active and reactive power
|
Supply voltage
|
90...450 V AC 45...65 Hz
100...300 V DC
|
Network frequency
|
50 Hz
60 Hz
|
[In] rated current
|
1 A
5 A
|
Type of network
|
1P + N
3P
3P + N
|
Maximum power consumption in VA
|
11 VA at 415 V
|
Ride-through time
|
80 ms 120 V AC typical
100 ms 230 V AC typical
100 ms 415 V AC typical
50 ms 125 V DC typical
|
Display type
|
Monochrome graphic LCD
|
Display resolution
|
128 x 128 pixels
|
Sampling rate
|
64 samples/cycle
|
Measurement current
|
5…8500 mA
|
Analogue input type
|
Voltage (impedance 5 MOhm)
Current (impedance <= 0.3 mOhm)
|
Measurement voltage
|
35…760 V AC 45...65 Hz between phases
20…440 V AC 45...65 Hz between phase and neutral
|
Frequency measurement range
|
45…65 Hz
|
Number of inputs
|
2 digital
|
Measurement accuracy
|
Active energy +/- 0.5 %
Reactive energy +/- 2 %
Active power +/- 0.5 %
Apparent power +/- 0.5 %
Frequency +/- 0.05 %
Power factor +/- 0.5
Current +/- 0.5 %
Voltage +/- 0.5 %
Apparent energy +/- 0.5 %
Reactive power +/- 2 %
|
Accuracy class
|
Class 0.5S active energy conforming to IEC 62053-22
|
Number of outputs
|
2 digital
|
Information displayed
|
Tariff (4)
|
Communication port protocol
|
Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires, insulation 2500 V
JBUS
|
Communication port support
|
RS485
|
Data recording
|
Event logs
Min/max of instantaneous values
Alarm logs
Data logs
Time stamping
Maintenance logs
|
Memory capacity
|
256 kB
|
Connections - terminals
|
Voltage circuit: screw terminal block4
Control circuit: screw terminal block2
Current transformer: screw terminal block6
Input/output circuit: screw terminal block6
Relay output: screw terminal block4
Ethernet network: RJ45 connector
|
Mounting mode
|
Flush-mounted
|
Mounting support
|
Framework
|
Standards
|
EN 50470-3
IEC 62053-24
IEC 60529
EN 50470-1
UL 61010-1
IEC 62053-22:2020
IEC 61557-12:2015
IEC 62053-23:2020
IEC 62052-11:2020
IEC 62052-31:2015
|
Product certifications
|
CE conforming to IEC 61010-1
CULus conforming to UL 61010-1
|
Width
|
96 mm
|
Depth
|
72 mm
|
Height
|
96 mm
|
Net weight
|
430 g
|
Electromagnetic compatibility
|
Conducted and radiated emissions class A conforming to EN 55011
Limits for harmonic current emissions class A conforming to IEC 61000-3-2
Immunity to conducted disturbances - test level: 150 kHz...80 MHz level 3 conforming to IEC 61000-4-6
Voltage dips and interruptions immunity test level 4 conforming to IEC 61000-4-11
Conducted RF disturbances level 3 conforming to IEC 61000-4-6
Magnetic field at power frequency level 4 conforming to IEC 61000-4-8
Conducted and radiated emissions class B conforming to EN 55022
Limitation of voltage changes, voltage fluctuations and flicker in low-voltage conforming to IEC 61000-3-3
Electrostatic discharge - test level: 8 kV level 4 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
Surge immunity test level 4 conforming to IEC 61000-4-5
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
|
IP degree of protection
|
IP54 display: conforming to IEC 60529
IP30 rear: conforming to IEC 60529
|
Relative humidity
|
5…95 % at 50 °C non-condensing
|
Pollution degree
|
2
|
Ambient air temperature for operation
|
-25…70 °C meter
-20…70 °C display
-25…-20 °C (with reduced performance) display
|
Ambient air temperature for storage
|
-40…85 °C
|
Operating altitude
|
2000 m CAT III
3000 m CAT II
|