NSYCVF165M24DPF
ClimaSys forced vent. IP54, 188m3/h, 24V DC, with outlet grille and filter G2
|
|
|
Main
Range
|
ClimaSys
|
Product name
|
ClimaSys CV
|
Product or component type
|
Fan
|
Type of filter
|
Standard
|
Flow rate
|
Free flow rate with standard filter: 188 m3/h
|
[Us] rated supply voltage
|
10...27.6 V
|
Input voltage
|
24 V DC
|
Complementary
Absorbed power
|
8 W
|
[In] rated current
|
0.3 A
|
Noise level < at
|
50…51 dB
|
Bearing type
|
Ball
|
Height
|
External: 268 mm
|
Width
|
External: 248 mm
|
Depth
|
External : 104 mm
|
Cut-out dimensions
|
223 x 223 mm
|
Net weight
|
0.81 kg
|
Material
|
Outlet grille: injected thermoplastic (ASA PC)
|
Colour
|
Outlet grille: grey (RAL 7035)
|
Ambient air temperature for operation
|
-10…70 °C
|
Ambient air temperature for storage
|
-40…70 °C
|
Maximum pressure
|
50 Pa flow rate 0 m³/h
|
Connections - terminals
|
Cable
|
IP degree of protection
|
IP54
|
Device composition
|
1 axial motor
2 protective grille: on the front and rear surfaces
1 filter: front of axial motor
1 outlet grille: front
1 cut-out template
1 power cord
|
Condition of use
|
Surrounding environment must be relatively clean
Flow rates depends on the work point, see ProClima software
Overfrequent filter replacement should be avoided
Filter must be cleaned and replaced regularly
Outside temperature must be 5 °C lower than inside temperature
|
Packing Units
Unit Type of Package 1
|
PCE
|
Number of Units in Package 1
|
1
|
Package 1 Height
|
18.500 cm
|
Package 1 Width
|
25.000 cm
|
Package 1 Length
|
27.000 cm
|
Package 1 Weight
|
1.068 kg
|
Unit Type of Package 2
|
P12
|
Number of Units in Package 2
|
64
|
Package 2 Height
|
120.000 cm
|
Package 2 Width
|
80.000 cm
|
Package 2 Length
|
120.000 cm
|
Package 2 Weight
|
80.000 kg
|
Offer Sustainability