NSYCVF38M48DPF
ClimaSys forced vent. IP54, 44m3/h, 48V DC, with outlet grille and filter G2
|
|
|
Main
Range
|
ClimaSys
|
Product name
|
ClimaSys CV
|
Product or component type
|
Fan
|
Type of filter
|
Standard
|
Flow rate
|
Free flow rate with standard filter: 44 m3/h
|
[Us] rated supply voltage
|
36...56 V
|
Input voltage
|
48 V DC
|
Complementary
Absorbed power
|
3.6 W
|
[In] rated current
|
0.07 A
|
Noise level < at
|
40…41 dB
|
Bearing type
|
Ball
|
Height
|
External: 137 mm
|
Width
|
External: 117 mm
|
Depth
|
External : 49 mm
|
Cut-out dimensions
|
92 x 92 mm
|
Net weight
|
0.23 kg
|
Material
|
Outlet grille: injected thermoplastic (ASA PC)
|
Colour
|
Outlet grille: grey (RAL 7035)
|
Ambient air temperature for operation
|
-10…70 °C
|
Ambient air temperature for storage
|
-40…70 °C
|
Maximum pressure
|
29 Pa flow rate 0 m³/h
|
Connections - terminals
|
Cable
|
IP degree of protection
|
IP54
|
Device composition
|
1 axial motor
2 protective grille: on the front and rear surfaces
1 filter: front of axial motor
1 outlet grille: front
1 cut-out template
|
Condition of use
|
Outside temperature must be 5 °C lower than inside temperature
Surrounding environment must be relatively clean
Overfrequent filter replacement should be avoided
Flow rates depends on the work point, see ProClima software
Filter must be cleaned and replaced regularly
|
Packing Units
Unit Type of Package 1
|
PCE
|
Number of Units in Package 1
|
1
|
Package 1 Height
|
7.000 cm
|
Package 1 Width
|
12.500 cm
|
Package 1 Length
|
14.700 cm
|
Package 1 Weight
|
280.000 g
|
Offer Sustainability