|
|
|
NSYCVF560M230PF
ClimaSys forced vent. IP54, 560m3/h, 230V, with outlet grille and filter G2
|
|
|
Overview
Lead time
|
Usually Ships within 4 Weeks
|
Main
Range
|
ClimaSys
|
Product name
|
ClimaSys CV
|
Product or component type
|
Fan
|
Range compatibility
|
Prisma P
Prisma G
|
Type of filter
|
Standard
|
Flow rate
|
Free flow rate with standard filter: 562 m3/h at 50 Hz
Free flow rate with standard filter: 586 m3/h at 60 Hz
|
[Us] rated supply voltage
|
207...244 V
|
Input voltage
|
230 V 50/60 Hz
|
Complementary
Absorbed power
|
65 W 50 Hz
80 W 60 Hz
|
[In] rated current
|
0.29 A 50 Hz
0.35 A 60 Hz
|
Noise level < at
|
59 dB
|
Bearing type
|
Ball
|
Height
|
External: 336 mm
|
Width
|
External: 316 mm
|
Depth
|
External : 161 mm
|
Cut-out dimensions
|
291 x 291 mm
|
Net weight
|
3.2 kg
|
Material
|
Outlet grille: injected thermoplastic (ASA PC)
|
Colour
|
Outlet grille: grey (RAL 7035)
|
Ambient air temperature for operation
|
-15…60 °C
|
Ambient air temperature for storage
|
-40…70 °C
|
Maximum pressure
|
140 Pa flow rate 0 m³/h
|
Connections - terminals
|
Terminal block
|
IP degree of protection
|
IP54
|
Device composition
|
1 axial motor
2 protective grille: on the front and rear surfaces
1 filter: front of axial motor
1 outlet grille: front
1 cut-out template
|
Condition of use
|
Filter must be cleaned and replaced regularly
Surrounding environment must be relatively clean
Outside temperature must be 5 °C lower than inside temperature
Overfrequent filter replacement should be avoided
Flow rates depends on the work point, see ProClima software
|
Packing Units
Unit Type of Package 1
|
PCE
|
Number of Units in Package 1
|
1
|
Package 1 Height
|
23.000 cm
|
Package 1 Width
|
32.000 cm
|
Package 1 Length
|
34.000 cm
|
Package 1 Weight
|
3.554 kg
|
Unit Type of Package 2
|
P12
|
Number of Units in Package 2
|
24
|
Package 2 Height
|
119.000 cm
|
Package 2 Width
|
80.000 cm
|
Package 2 Length
|
120.000 cm
|
Package 2 Weight
|
94.000 kg
|
Offer Sustainability
Contractual warranty
|
|