|
|
|
NSYCVF850M400PF
ClimaSys forced vent. IP54, 850m3/h, 400V, with outlet grille and filter G2
|
|
|
Main
Range
|
ClimaSys
|
Product name
|
ClimaSys CV
|
Product or component type
|
Fan
|
Type of filter
|
Standard
|
Flow rate
|
Free flow rate with standard filter: 803 m3/h at 60 Hz
Free flow rate with standard filter: 931 m3/h at 50 Hz
|
[Us] rated supply voltage
|
396...466 V
|
Input voltage
|
400 V 50/60 Hz
|
Complementary
Absorbed power
|
126 W 50 Hz
126 W 60 Hz
|
[In] rated current
|
0.21 A 50 Hz
0.26 A 60 Hz
|
Noise level < at
|
75…77 dB
|
Bearing type
|
Ball
|
Height
|
External: 336 mm
|
Width
|
External: 316 mm
|
Depth
|
External : 162 mm
|
Cut-out dimensions
|
291 x 291 mm
|
Net weight
|
4.1 kg
|
Material
|
Outlet grille: injected thermoplastic (ASA PC)
|
Colour
|
Outlet grille: grey (RAL 7035)
|
Ambient air temperature for operation
|
-15…60 °C
|
Ambient air temperature for storage
|
-40…70 °C
|
Maximum pressure
|
170 Pa flow rate 0 m³/h
|
Connections - terminals
|
Terminal block
|
IP degree of protection
|
IP54
|
Device composition
|
1 axial motor
2 protective grille: on the front and rear surfaces
1 filter: front of axial motor
1 outlet grille: front
1 cut-out template
|
Condition of use
|
Outside temperature must be 5 °C lower than inside temperature
Overfrequent filter replacement should be avoided
Flow rates depends on the work point, see ProClima software
Filter must be cleaned and replaced regularly
Surrounding environment must be relatively clean
|
Packing Units
Unit Type of Package 1
|
PCE
|
Number of Units in Package 1
|
1
|
Package 1 Height
|
23.500 cm
|
Package 1 Width
|
32.500 cm
|
Package 1 Length
|
34.000 cm
|
Package 1 Weight
|
4.472 kg
|
Unit Type of Package 2
|
P12
|
Number of Units in Package 2
|
24
|
Package 2 Height
|
110.000 cm
|
Package 2 Width
|
80.000 cm
|
Package 2 Length
|
120.000 cm
|
Package 2 Weight
|
118.500 kg
|
Offer Sustainability
Contractual warranty
|
|