Concept
|
Transparent Ready
|
Port Ethernet
|
10BASE-T/10BASE-TX
|
Bus length
|
0…100 m, copper
|
Number of devices per segment
|
0…256
|
Communication service
|
Modbus messaging
|
Web services
|
No standard Web server
|
Discrete input voltage
|
24 V
|
Discrete input voltage type
|
DC
|
Discrete input type
|
NPN or PNP
|
Input voltage limits
|
20.4...26.4 V
|
Electronic filtering time
|
0.035 ms for I0...I1 at state 1
0.035 ms for I6...I7 at state 1
0.04 ms for I2...I5 at state 1
0.04 ms for I8...I11 at state 1
0.045 ms for I0...I1 at state 0
0.045 ms for I6...I7 at state 0
0.15 ms for I2...I5 at state 0
0.15 ms for I8...I11 at state 0
|
Configurable filtering time
|
0 ms
3 ms
12 ms
|
Input impedance
|
3.4 kOhm for I2...I5
3.4 kOhm for I8...I11
5.7 kOhm for I0...I1
5.7 kOhm for I6...I7
|
Discrete output voltage
|
24 V DC solid state output(s)
240 V AC relay output(s)
30 V DC relay output(s)
|
Output voltage limits
|
20.4...28.8 V solid state
|
Maximum output current
|
360 mA, solid state
|
Maximum current per output common
|
8 A relay
0.72 A solid state
|
Current consumption
|
30 mA at 5 V DC (at state 1) relay output
40 mA at 24 V DC (at state 1) relay output
5 mA at 5 V DC (at state 0) relay output
|
Output overvoltage protection
|
38...40 V
|
Maximum tungsten load
|
<8 W for solid state
|
Response time
|
300 µs at state 0 for relay
300 µs at state 1 for relay
5 µs at state 0 for solid state
5 µs at state 1 for solid state
|
Minimum switchable load
|
0.1 mA
|
Contact bounce time
|
<= 1 ms for relay
|
Maximum leakage current
|
0.1 mA at state 0 for solid state
|
Drop-out voltage
|
1 V at state 1
|
Insulation between channel and internal logic
|
1500 Vrms for 1 minute for relay output
500 Vrms for 1 minute for input circuit
500 Vrms for 1 minute for solid state output
|
Insulation between channels
|
None
|
Contact resistance
|
30 mOhm
|
Electrical durability
|
500000 cycles AC-1 with 500 VA load for relay output
500000 cycles AC-14 with 250 VA load for relay output
500000 cycles AC-15 with 200 VA load for relay output
500000 cycles DC-1 with 60 W load for relay output
500000 cycles DC-13 with 30 W load for relay output
|
Supply circuit type
|
DC
|
[Us] rated supply voltage
|
24 V
|
Supply voltage limits
|
20.4…26.2 V
|
Input current
|
700 mA at 26.2 V for supply circuit
|
Inrush current
|
1 A for solid state output
50 A for supply circuit
|
Power consumption in W
|
19 W
|
Maximum number of I/O expansion module
|
7
|
I/O expansion capacity
|
132 with screw terminal discrete I/O module(s)
188 with spring terminal discrete I/O module(s)
244 with HE10 connector discrete I/O module(s)
7 x 8I or 7 x 2I or 7 x (4I/2O) with screw terminal analogue I/O module(s)
|
Insulation resistance
|
>= 10 MOhm between I/O and earth terminals
>= 10 MOhm between power supply and earth
|
I/O connection
|
Removable screw terminal block
|
Number of common point
|
1 for relay output (1 NO)
1 for relay output (2 NO)
1 for relay output (3 NO)
1 for input
1 for solid state output
|
Counting input number
|
2
|
Counting capacity
|
32 bits
|
Counting frequency
|
5000 Hz
20000 Hz
|
Pulse generator number
|
2
|
Pulse generator frequency
|
7 kHz
|
Pulse generator function
|
RPLS pulse generator output
RPWM pulse width modulation
|
Marking
|
CE
|
Fixing mode
|
By clips (35 mm symmetrical DIN rail)
By screws (panel with fixing kit)
By screws (solid plate with fixing kit)
|
Status LED
|
1 LED per channel (green) I/O
1 LED (green) 10T
1 LED (green) PWR
1 LED (yellow) 100T
1 LED (yellow) STAT
|
Net weight
|
0.185 kg
|
IP degree of protection
|
IP20
|
Immunity to microbreaks
|
10 ms for supply circuit
|
Dielectric strength
|
500 V between I/O and earth terminals
500 V between power supply and earth
|
Standards
|
CSA
CSA C22.2 No 213 Class I Division 2 Group B
CSA C22.2 No 213 Class I Division 2 Group A
UL 508
CSA C22.2 No 213 Class I Division 2 Group C
EN 61131-2
CSA C22.2 No 213 Class I Division 2 Group D
IEC 61131-2
|
Product certifications
|
cULus
|
Ambient air temperature for operation
|
0…55 °C
|
Ambient air temperature for storage
|
-25…70 °C
|
Relative humidity
|
30…95 % without condensation
|
Pollution degree
|
2 conforming to EN 60664
2 conforming to IEC 60664
|
Operating altitude
|
0...2000 m
|
Storage altitude
|
0…3000 m
|
Vibration resistance
|
0.075 mm at 10…57 Hz on 35 mm symmetrical DIN rail
1 gn at 57…150 Hz on 35 mm symmetrical DIN rail
|
Shock resistance
|
15 gn for 11 ms conforming to EN 61131
15 gn for 11 ms conforming to IEC 61131
|
Resistance to electrostatic discharge
|
4 kV in contact conforming to IEC 61000-4-2
8 kV in air conforming to EN 61000-4-2
8 kV in air conforming to IEC 61000-4-2
4 kV in contact conforming to EN 61000-4-2
|
Resistance to radiated fields
|
10 V/m, radio frequency fields = 80000000…2000000000 Hz conforming to EN 61000-4-3
10 V/m, radio frequency fields = 80000000…2000000000 Hz conforming to IEC 61000-4-3
|
Resistance to fast transients
|
1 kV (24 V solid state I/O) conforming to IEC 61000-4-4
2 kV (24 V supply) conforming to IEC 61000-4-4
|