Surge arrester class type
|
Type 2
|
Surge arrester technology
|
MOV + GDT
|
[Ue] rated operational voltage
|
230/400 V +/- 10 % AC 50/60 Hz
|
[In] nominal discharge current
|
Differential mode: 5 kA (L/N)
Common mode: 20 kA (N/PE)
|
[Imax] maximum discharge current
|
Differential mode: 10 kA L/N
Common mode: 20 kA N/PE
|
[Uc] maximum continuous operating voltage
|
Common mode: 275 V N/PE
Differential mode: 275 V L/N
|
Response time
|
<= 25 ns
|
Maximum [Up] voltage protection level
|
Common mode <1.5 kV type 2 N/PE
Differential mode <1.5 kV type 2 L/N
|
[Ut] temporary overvoltage
|
337 V L/N 5 s withstand
1200 V N/PE 200 ms safe failure mode
442 V L/PE 5 s withstand
|
[Ifi] follow current
|
0.1 kA common mode N/PE
|
[Isccr] short-circuit current rating
|
6 kA
|
Local signalling
|
White/red flag
|
Disconnector device type
|
Integrated circuit breaker - Icu 6 kA
|
Mounting mode
|
Clip-on
|
Mounting support
|
DIN rail
|
9 mm pitches
|
10
|
Height
|
106.8 mm
|
Width
|
88.4 mm
|
Depth
|
74.1 mm
|
Colour
|
White (RAL 9003)
|
Maximum residual current
|
1 mA
|
Connections - terminals
|
Tunnel type terminal (L/N) 1…16 mm² rigid
Tunnel type terminal (L/N) 1…10 mm² flexible
Tunnel type terminal (ground) 6…25 mm² rigid
Tunnel type terminal (ground) 6…16 mm² flexible with ferrule
|
Tightening torque
|
2 N.m
|
Provided equipment
|
Pre-fitted PE earth cable
1 intermediary terminal block
|