|
|
|
RE17LAMW
single function relay, Harmony Timer Relays, 0.7A, 1CO, 0,1s..100h, on delay, solid state output, 24..240V AC DC
|
|
|
Main
Range of product
|
Harmony Timer Relays
|
Discrete output type
|
Solid state
|
Width
|
17.5 mm
|
Product or component type
|
Single function relay
|
Component name
|
RE17L
|
Time delay range
|
1...10 s
10...100 h
6...60 s
0.1...1 s
1...10 min
6...60 min
1...10 h
|
Nominal output current
|
0.7 A
|
Complementary
Control type
|
Selector switch front panel
|
[Us] rated supply voltage
|
24...240 V AC/DC 50/60 Hz
|
Voltage range
|
0.85...1.1 Us
|
Supply frequency
|
50...60 Hz +/- 5 %
|
Control signal pulse width
|
0.05 s typical
|
Insulation resistance
|
100 MOhm at 500 V DC conforming to IEC 60664-1
|
[Uimp] rated impulse withstand voltage
|
5 kV during 1.2/50 µs
|
Power on delay
|
100 ms
|
Connections - terminals
|
Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
|
Tightening torque
|
0.6…1 N.m conforming to IEC 60947-1
|
Dielectric strength
|
2.5 kV 1 mA/1 minute 50 Hz conforming to IEC 61812-1
|
Housing material
|
Self-extinguishing
|
Repeat accuracy
|
+/- 0.5 % conforming to IEC 61812-1
|
Temperature drift
|
+/- 0.05 %/°C
|
Voltage drift
|
+/- 0.2 %/V
|
Setting accuracy of time delay
|
+/- 10 % of full scale at 25 °C conforming to IEC 61812-1
|
Time delay type
|
Power on-delay - A- Power on-delay relay
|
Reset time
|
350 ms on de-energisation typical
|
On-load factor
|
100 %
|
Power consumption in VA
|
0…3 VA at 240 V AC
|
Maximum power consumption in W
|
1.5 W at 240 V DC
|
Breaking capacity
|
0.5 A AC/DC conforming to UL
0.7 A AC/DC at 20 °C
|
Operating frequency
|
10 Hz
|
Maximum output current
|
20 A
|
Minimum switching current
|
10 mA
|
Maximum leakage current
|
5 mA
|
Maximum switching voltage
|
250 V AC/DC
|
Maximum voltage drop
|
<4 V 3-wire
<8 V 2-wire
|
Electrical durability
|
100000000 cycles
|
Marking
|
CE
|
Creepage distance
|
4 kV/3 conforming to IEC 60664-1
|
Safety reliability data
|
MTTFd = 353.8 years
B10d = 320000
|
Mounting position
|
Any position in relation to normal vertical mounting plane
|
Mounting support
|
35 mm DIN rail conforming to IEC 60715
|
Function available
|
A- Power on-delay relay-1 solid state output
|
Control type
|
Without test button
|
Net weight
|
0.068 kg
|
Time delay type
|
A
|
Functionality
|
On-delay timing
|
Number of functions
|
1
|
Compatibility code
|
RE17
|
Environment
Immunity to microbreaks
|
20 ms
|
Derating factor
|
5 mA/°C
|
Standards
|
2004/108/EC
IEC 61000-6-1
2006/95/EC
IEC 61000-6-3
IEC 61000-6-2
IEC 61812-1
IEC 61000-6-4
|
Product certifications
|
GL
CSA
cULus
|
Ambient air temperature for storage
|
-30…60 °C
|
Ambient air temperature for operation
|
-20…60 °C
|
IP degree of protection
|
IP20 (terminal block) conforming to IEC 60529
IP40 (housing) conforming to IEC 60529
IP50 (front panel) conforming to IEC 60529
|
Vibration resistance
|
20 m/s² (f= 10…150 Hz) conforming to IEC 60068-2-6
|
Shock resistance
|
15 gn for 11 ms conforming to IEC 60068-2-27
|
Relative humidity
|
93 % without condensation conforming to IEC 60068-2-30
|
Electromagnetic compatibility
|
Electrostatic discharge immunity test: (in contact), level 3, 6 kV, conforming to IEC 61000-4-2
Electrostatic discharge immunity test: (in air), level 3, 8 kV, conforming to IEC 61000-4-2
Susceptibility to electromagnetic fields: (80 MHz to 1 GHz), level 3, 10 V/m, conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test: (capacitive connecting clip), level 3, 1 kV, conforming to IEC 61000-4-4
Electrical fast transient/burst immunity test: (direct), level 3, 2 kV, conforming to IEC 61000-4-4
1.2/50 µs shock waves immunity test: (differential mode), level 3, 1 kV, conforming to IEC 61000-4-5
1.2/50 µs shock waves immunity test: (common mode), level 3, 2 kV, conforming to IEC 61000-4-5
Conducted RF disturbances: (0.15...80 MHz), level 3, 10 V, conforming to IEC 61000-4-6
Voltage dips and interruptions immunity test: (1 cycle), 0 %, conforming to IEC 61000-4-11
Voltage dips and interruptions immunity test: (25/30 cycles), 70 %, conforming to IEC 61000-4-11
Conducted and radiated emissions: , class B, conforming to EN 55022
|
Packing Units
Unit Type of Package 1
|
PCE
|
Number of Units in Package 1
|
1
|
Package 1 Height
|
2.600 cm
|
Package 1 Width
|
7.800 cm
|
Package 1 Length
|
9.500 cm
|
Package 1 Weight
|
70.000 g
|
Unit Type of Package 2
|
S02
|
Number of Units in Package 2
|
40
|
Package 2 Height
|
15.000 cm
|
Package 2 Width
|
30.000 cm
|
Package 2 Length
|
40.000 cm
|
Package 2 Weight
|
3.270 kg
|
Offer Sustainability
Packaging without single use plastic
|
Yes
|
Packaging made with recycled cardboard
|
Yes
|
SCIP Number
|
7bdc2711-0ad2-427c-8ece-532c5e9f09d7
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Pro-active compliance (Product out of EU RoHS legal scope)
|
Mercury free
|
Yes
|
Sustainable packaging
|
Yes
|
RoHS exemption information
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
California proposition 65
|
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
|
Take-back
|
No
|
Carbon footprint (kg.eq.CO2 per CR, Total Life cycle)
|
73
|
|
|