Reset time
|
1500 ms time delay
|
Maximum switching voltage
|
250 V AC/DC
|
Minimum switching current
|
10 mA at 5 V DC
|
Maximum switching current
|
5 A AC/DC
|
Supply voltage limits
|
183…528 V AC
|
Power consumption in VA
|
0…22 VA at 400 V AC 50 Hz
|
Control circuit frequency
|
50...60 Hz +/- 10 %
|
Voltage detection threshold
|
183 V
|
Output contacts
|
1 C/O
|
Nominal output current
|
5 A
|
Hysteresis
|
2 %
|
Measurement accuracy
|
+/- 10 % of the full scale value
|
Delay at power up
|
650 ms
|
Maximum measuring cycle
|
150 ms measurement cycle as true rms value
|
Threshold adjustment voltage
|
2...20 % of Un selected
-2...-17 % in the range 220 V AC
+2...+10 % in the range 480 V AC
-2...-12 % in the range 208 V AC
|
Repeat accuracy
|
+/- 0.5 % for input and measurement circuit
+/- 1 % for time delay
|
Measurement error
|
< 1 % over the whole range with voltage variation
0.05 %/°C with temperature variation
|
Response time
|
< 200 ms (in the event of a fault)
|
Quality labels
|
CE
|
Insulation resistance
|
> 500 MOhm at 500 V DC conforming to IEC 60255-5
> 500 MOhm at 500 V DC conforming to IEC 60664-1
|
Operating position
|
Any position without derating
|
Local signalling
|
LED (green) for power ON
LED (yellow) for relay ON
|
Overvoltage category
|
III conforming to IEC 60664-1
|
[Ui] rated insulation voltage
|
400 V conforming to IEC 60664-1
|
Connections - terminals
|
Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...2 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
|
Tightening torque
|
0.6…1 N.m conforming to IEC 60947-1
|
Housing material
|
Self-extinguishing plastic
|
Mounting support
|
35 mm symmetrical DIN rail conforming to IEC 60715
|
Electrical durability
|
100000 cycles
|
Mechanical durability
|
30000000 cycles
|
Operating rate
|
<= 360 operations/hour full load
|
Utilisation category
|
AC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
DC-12 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
DC-14 conforming to IEC 60947-5-1
|
[Un] rated nominal voltage
|
, self-powered
|
Safety reliability data
|
B10d = 470000
MTTFd = 502.2 years
|
Control type
|
Without test button
|
Width
|
17.5 mm
|
Net weight
|
0.08 kg
|
Electromagnetic compatibility
|
Emission standard for industrial environments conforming to IEC 61000-6-4
Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3
Immunity for industrial environments conforming to NF EN/IEC 61000-6-2
|
Ambient air temperature for operation
|
-20…50 °C
|
Vibration resistance
|
0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6
1 gn (f= 57.6…150 Hz) conforming to IEC 60255-21-1
|
Shock resistance
|
5 gn conforming to IEC 60068-2-27
|
Standards
|
IEC 60255-1
|
Product certifications
|
GOST
UL
GL
C-Tick
CSA
|
Ambient air temperature for storage
|
-40…70 °C
|
Relative humidity
|
95 % at 55 °C conforming to IEC 60068-2-30
|
IP degree of protection
|
IP20 (terminals) conforming to IEC 60529
IP30 (casing) conforming to IEC 60529
|
Pollution degree
|
3 conforming to IEC 60664-1
|
Directives
|
89/336/EEC - electromagnetic compatibility
73/23/EEC - low voltage directive
|
Dielectric test voltage
|
2 kV, 1 min AC 50 Hz
|
Non-dissipating shock wave
|
4 kV
|
SCIP Number
|
Ba9cbb5b-722a-41d2-b7d0-f60d5f3f104d
|
Packaging without single use plastic
|
Yes
|
Packaging made with recycled cardboard
|
Yes
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Pro-active compliance (Product out of EU RoHS legal scope)
|
Mercury free
|
Yes
|
Sustainable packaging
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
RoHS exemption information
|
Yes
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
California proposition 65
|
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
|
Take-back
|
No
|
Carbon footprint (kg.eq.CO2 per CR, Total Life cycle)
|
98
|