Range of product
|
Harmony Control Relays
|
Relay type
|
Temperature control relays
|
Product or component type
|
Elevator machine room temperature control relay
|
Product specific application
|
For elevator machine rooms and 3-phase supplies
|
Relay name
|
RM35AT
|
Relay monitored parameters
|
Phase sequence
Phase failure detection
Undertemperature: -1...11°C
Overtemperature: 34...46°C
|
Time delay range
|
0.1...10 s adjustable delay (tolerance: 0...10 % of the full scale value)
|
Switching capacity in VA
|
1250 VA
|
Minimum switching current
|
10 mA at 5 V DC
|
Maximum power consumption in VA
|
3.5 VA AC
|
Utilisation category
|
AC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
DC-12 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
DC-14 conforming to IEC 60947-5-1
|
Time delay
|
Adjustable 1...10 s Tt- time delay upon fault
|
Measurement range
|
208...480 V AC
+/- 1...46 °C
|
Reset time
|
8 s
|
Maximum switching voltage
|
250 V AC/DC
|
[Us] rated supply voltage
|
24...240 V AC/DC
|
[Un] rated nominal voltage
|
24...240 V AC/DC 50/60 Hz, non self-powered
|
Supply voltage limits
|
20.4…264 V AC
21.6…264 V DC
|
Maximum power consumption in W
|
0.6 W DC
|
Resistance across terminals
|
600 kOhm at 3-phase
1.33 kOhm at temperature
|
Width
|
35 mm
|
Output contacts
|
2 NO
|
Contacts material
|
Cadmium free
|
Nominal output current
|
5 A
|
Delay at power up
|
0.2 s
|
Measurement accuracy
|
+/- 2 °C
|
Response time
|
<= 3.5 s + Tt (in case of temperature fault)
500 ms (in case of 3-phase fault)
500 ms (on disappearance of fault)
|
Temperature probe type
|
Pt 100 - 3-wire
|
Installed device
|
Pt 100 probe cable length <= 10 m
|
Marking
|
CE : EMC 89/336/EEC
CE : 73/23/EEC
|
Overvoltage category
|
III conforming to IEC 60664-1
|
Insulation resistance
|
> 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5
> 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1
> 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5
> 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1
> 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5
> 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1
|
[Ui] rated insulation voltage
|
400 V conforming to IEC 60664-1
|
Operating voltage tolerance
|
- 10 % + 10 % Un DC
- 15 % + 10 % Un AC
|
Supply frequency
|
50/60 Hz +/- 10 %
|
Operating position
|
Any position without derating
|
Connections - terminals
|
Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
|
Tightening torque
|
0.6…1 N.m conforming to IEC 60947-1
|
Housing material
|
Self-extinguishing plastic
|
Local signalling
|
1 LED green for power ON
1 LED yellow for correct temperature (high R1)/(low R2)
1 LED yellow for phases of relay
|
Mounting support
|
35 mm symmetrical DIN rail conforming to IEC 60715
|
Electrical durability
|
100000 cycles
|
Mechanical durability
|
30000000 cycles
|
Operating rate
|
<= 360 operations/hour full load
|
Control type
|
Without test button
|
Immunity to microbreaks
|
10 ms
|
Electromagnetic compatibility
|
Emission standard for industrial environments conforming to IEC 61000-6-4
Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3
Immunity for industrial environments conforming to NF EN/IEC 61000-6-2
|
Standards
|
NF EN 60255-6
IEC 60255-6
|
Product certifications
|
GL
UL
C-Tick
CSA
GOST
|
Ambient air temperature for storage
|
-40…70 °C
|
Ambient air temperature for operation
|
-20…50 °C
|
Vibration resistance
|
0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1
1 gn (f= 57.6…150 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1
|
Shock resistance
|
15 gn for 11 ms conforming to IEC 60255-21-1
|
IP degree of protection
|
IP20 (terminals) conforming to IEC 60529
IP30 (casing) conforming to IEC 60529
|
Pollution degree
|
3 conforming to IEC 60664-1
|
Dielectric test voltage
|
2 kV, 1 min AC 50 Hz
|
Non-dissipating shock wave
|
4 kV
|